Lochinvar ProtoNode Start-up Guide
Page 49 of 56
Manual Reset High Limit
BI
3
DI
3
Flow Switch
BI
4
DI
4
Gas Pressure Switch
BI
5
DI
5
Louvers Proving Switch
BI
6
DI
6
Blower Proving Switch 1
BI
7
DI
7
Blocked Drain Switch
BI
8
DI
8
Flame 1
BI
9
DI
9
Enable
BI
10
DI
10
Tank Thermostat
BI
11
DI
11
Blocked Flue
BI
12
DI
12
Blower Proving Switch 2
BI
13
DI
13
Flue Damper Proving Switch
BI
14
DI
14
Flame 2
BI
15
DI
15
Run Time Contacts
BI
16
DI
16
Alarm Contacts
BI
17
DI
17
SH Pump
BI
18
DI
18
HWG Pump
BI
19
DI
19
Louver Relay
BI
20
DI
20
Gas Valve 1
BI
21
DI
21
System Pump
BI
22
DI
22
Vent Damper Relay
BI
23
DI
23
Gas Valve 2
BI
24
DI
24
Blower #1 Power
BI
25
DI
25
Blower #2 Power
BI
26
DI
26
Spark Igniter
BI
27
DI
27
Transition Gas Valve
BI
28
DI
28
Air Valve Trigger
BI
29
DI
29
Air Valve Proving
BI
30
DI
30
Discrete Inputs 01-16
AI
31
AI
31
Discrete Inputs 17-32
AI
32
AI
32
Discrete Inputs 33-48
AI
33
AI
33
System Cascade Setpoint
AI
34
AI
34
System Pump Speed In
AI
35
AI
35
Cascade Total Power
AI
36
AI
36
Cascade Current Power
AI
37
AI
37
Outlet Setpoint
AI
38
AI
38
Outlet Temperature
AI
39
AI
39
Inlet Temperature
AI
40
AI
40
Flue Temperature
AI
41
AI
41
Firing Rate
AI
42
AI
42
Boiler Pump Speed Out
AI
43
AI
43
Boiler Status Code
AI
44
AI
44
Boiler Blocking Code
AI
45
AI
45
Boiler Lock Out Code
AI
46
AI
46
Discrete Inputs 49-64
AI
47
AI
47
Lockout Error Leader
AI
48
AI
48
Lockout Error Member 1
AI
49
AI
49
Lockout Error Member 2
AI
50
AI
50
Lockout Error Member 3
AI
51
AI
51
Lockout Error Member 4
AI
52
AI
52
Lockout Error Member 5
AI
53
AI
53
Lockout Error Member 6
AI
54
AI
54
Lockout Error Member 7
AI
55
AI
55
Configuration
AV
56
AO
56
Coils
AV
57
AO
57
0-10 Volt Input
AV
58
AO
58
Tank Setpoint
AV
59
AO
59
Tank Temperature
AV
60
AO
60
Outdoor Temperature
AV
61
AO
61
System Supply Temperature
AV
62
AO
62
System Return Temperature
AV
63
AO
63