- 7 -
■
Communication specifications
Item
Specifications
Communication
IO-Link V1.1
IO-Link type
Device
IO-Link port type
Class A
Communication speed
230.4kbps
(
COM3
)
Message type(Pre-Operate)
TYPE_0
Message type (Operate)
TYPE_2_V (On-Request Data = 1octet = 1byte)
Service data(ISDU)
Available
Data storage function (DS)
Available
Block parameters
Available
Event
Available
Process data input(PDin: Sent from device)
6bytes
Process data output(PDout: Sent from master)
4bytes
Minimum cycle time(MinCycleTime)
2.5ms
■Process data
Process data is the cyclic data which is exchanged periodically between the base module and
device.
Process data consists of PD_IN (process data input); 4 BYTE and PD_OUT (process data
output); 2 BYTE as shown below.
-
The process data of this product is Big-Endian type.
When the transmission method of the upper communication is Little-Endian type, the BYTE
order will be changed.
Refer to the table below for the Endian type of the major upper communication.
Endian type
Upper communication protocol
Big-Endian type
PROFIBUS and PROFINET
Little-Endian type
EtherNET/IP, EtherCAT and CC-Link IE Field.
Process data input: 6 BYTE (device (ITV) --> base module)
Byte
No.
(Order)
Bit No.
(Order)
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Output pressure [High byte]
1
Output pressure [Low byte]
2
(Reserved): Not required.
3
(Reserved): Not required.
4
Diagnostic information
[High byte]
5
Diagnostic information
[Low byte]