Pressure display unit
Same functionality as via IO-Link. It is
possible to change the pressure display unit.
ITV*0*0-IL*0-*-M-X399 is from SI units,
ITV*0*0-IL*0-*-K-X399 is from SI units, bar,
psi, kgf/cm2 You can choose.
No
Key operation
LED Display
(1)
Deactivate the key lock if necessary (see page 22).
(2)
Press S-key for 2 seconds or more, then go to detail setting mode.
(3)
To "F04" by using the
△
and
▽
keys.
⇔
(displayed alternately)
(4)
Press S-key.
(5)
Set Pressure display unit by using the
△
and
▽
keys.
(blink and change the rightest digit)
*
Pressure display unit : refer to note2
(6)
Press S-key.
⇔
(displayed alternately)
(7)
Press S-key for 2 seconds or more, then go out from detail setting mode.
(Select the menu with
△
or
▽
keys, then jump to another item.)
(8)
Activate the key lock if necessary (see page 22).
(Note1)
:
Due to the new measurement law, please use only SI units in Japan.
(Note2
):
The relationship between the LED display by key operation and the pressure display
unit setting is as follows.
LED
Pressure display unit
U_0
MPa
U_1
kPa
U_2
Bar
U_3
PSI
U_4
kgf/cm
2
※
is the factory default value.
Only U_0 and U_1 can be selected for ITV*0*0-IL*0-*-M-X399.
※