HRX-OM-S010
Chapter 2 Contact input/output communication
2.4
Setting and checking
HRS100/150 Series
2-8
Contact input signal 2
Setting and checking
11.
Press the [SEL] key once.
The set screen of contact input signal 2
is displayed on the digital display.
12.
Select contact input signal 2 from the table below with [
▲] key or [▼] key, and confirm by
pressing “SEL”.
Table 2.4-7
List of set values
Set values
Explanation
Initial value
(Default setting)
Without signal input
○
Run/stop signal input
External switch signal input (N.O. type)
External switch signal input (N.C. type)
Remote signal input
1
1
:
When the setting of the serial protocol is “Simplified communication protocol 2”,
“Remote signal input” cannot be set.
Contact input signal 2 type
Setting and checking
13.
Press the [SEL] key once.
The set screen of contact input signal 2 type
is displayed on the digital display.
14.
Select contact input signal 2 type from the table below with [
▲] key or [▼] key, and confirm
by pressing
“SEL”.
Table 2.4-8
List of set values
Set values
Explanation
Initial value
(Default setting)
Setting/checking are not available if the
setting of contact input signal 2 is OFF.
Alternate signal
○
Momentary signal
1
1:Can be set when the setting of contact input signal 2 is "Run/Stop signal input" or "Remote
signal"
PV
SV
PV
SV