Chapter 4 Service Procedure
4.5 Replacement Procedure
HRS Series
4-58
<High pressure pump>
Removal (Between tank-pump)
1.
Discharge the circulating fluid referring the 4.2.2 Discharge of the circulating fluid and
facility water.
2.
Remove the upper panel and the panels on both sides referring the 4.2.1 Removal and the
mounting of the panel.
3.
Remove the hose clamp and remove hose.
For the HRS030-A, cut the cable tie which fixes the hose between the pump and
circulating fluid outlet port.
Fig. 4.5-43 Removal of plastic hose (Between tank-pump)
Mounting (Between tank-pump)
1.
Mount the hose using the hose clamp.
2.
Hold the hose with the hose clamp.
3.
Mount the upper panel and the panels on both sides in reversed order of removal.
For the HRS030-A, fix the hose between the pump and circulating fluid outlet port with a
cable tie to prevent the hose between the tank and pump from touching the fan motor
bracket.
2.
Hose clamp
3.
Hose
Pump
Tank
2.
Hose clamp
2.
Hose
Check the hose is not twisted after connecting.
3.
Cable tie
[For HRS030-A]