HRX-MM-L012
Chapter 4 Service Procedure
4.3 Replacement procedure
HRGC Series
4-16
Mounting
1.
Fix the pump. (Nut x 4)
2.
Fix the start-up capacitor with the tie wrap (2pcs).
3.
Mount the connector [JP] of the pump.
4.
Connect the ground wire. (Screw x 1)
5.
Apply the liquid gasket to the threads of pipes and mount them using a spanner/wrench
and pipe spanner/wrench.
[Key point]
z
Do not apply the liquid gasket to the first thread. Otherwise, the liquid
gasket will spread to the circulating circuit and cause the product to fail.
z
To prevent dust from getting caught in the threads, check there is no dust
stuck to the threads before the screw is mounted.
6.
Connect the hose A and tighten the hose band.
7.
Connect the hose B and tighten the hose band.
8.
Mount the temperature sensor.