HRX-MM-L012
Chapter 4 Service Procedure
HRGC Series
4.3 Replacement procedure
4-13
Mounting
1.
Fix the pump. (Nut x 4)
2.
Connect the hoses (2pcs) and tighten the wire hose bands.
[Key point]
Torque of wire hose band 3.0Nm
3.
Connect the ground wire. (Screw x 1)
4.
Mount the connector [JP] of the pump.
Check the hose is not twisted after connecting.