-20-
No.EX
※※
-OMW0016
Structure of Output Fault Action / Output Fault Value Parameter (index 84, 85)
Set the output (output 0 to output 31) at a IO-Link communication fault with two indexes.
For each output assignment, bit 0 corresponds to output 0 and bit 1 corresponds to output 1 by sub index.
Set the values below 2 bits for all outputs.
Index 84
Output Fault Action
Index 85
Output Fault Value
Output setting state at a communication fault
0
0
Clear Output (set 0)
0
1
Force Output (set 1)
1
x
Hold Last State
An example of setting is shown below.
Index 84
Output Fault Action
Index 85
Output Fault Value
Sub-Index Output
Output setting
Bit No. Value 7 6 5 4 3 2 1 0 Value 7 6 5 4 3 2 1 0
1
0-7
All clear output
Output
No.
-
7 6 5 4 3 2 1 0
-
7 6 5 4 3 2 1 0
Setting
value
00
0 0 0 0 0 0 0 0
00
0 0 0 0 0 0 0 0
2
8-15
All hold last state
Output
No.
-
15 14 13 12 11 10 9 8
-
15 14 13 12 11 10 9 8
Setting
value
FF
1 1 1 1 1 1 1 1
00
0 0 0 0 0 0 0 0
3
16-23
All force output
Output
No.
-
23 22 21 20 19 18 17 16
-
23 22 21 20 19 18 17 16
Setting
value
00
0 0 0 0 0 0 0 0
FF
1 1 1 1 1 1 1 1
4
24-31
Output 24-27:
Force output
Output 28-31:
Hold last state
Output
No.
-
31 30 29 28 27 26 25 24
-
31 30 29 28 27 26 25 24
Setting
value
F0
1 1 1 1 0 0 0 0
0F
0 0 0 0 1 1 1 1
Structure of Output Switching Counts (index68)
The output switching count parameter consists of thirty-two sub-indices that represent bit fields with a size
of 32 bits each. Sub-index 1 corresponds to output line 0 cycle count, Sub-index 2 to output line 1 cycle
count and so on.
The following shows an example of switching cycle count value 10.000.000 cycles according to the
transmission method of the upper communication.
10.000.000(dec) = 80 96 98 00 (hex)
(little endian)
10.000.000(dec) = 00 98 96 80 (hex)
(big endian)
*: For details of conditions that output switching count, refer to note out of the table in page
19
.