-18-
No.EX
※※
-OMW0016
Application Specific Parameters
Index
(dec)
Sub-
index
Access
1
Parameter name
Data
type
Default
Data
Storage
2
Description
0x54
(84)
1,2,3,4
R/W
Output Fault
Action
U8
{0,0,0,0}
Y
Determine how the SI unit
output act when a IO-Link
communication fault
(individual setting from
OUT0 to OUT31)
0:
Output Fault Value
parameter setting value
1
:
hold last state
0x55
(85)
1,2,3,4
R/W
Output Fault Value
U8
{0,0,0,0}
Y
If the Output Fault Action
parameter is set to 0, the
output of the SI unit
responds with a
user-defined fault value
when a communication
fault. (individual setting
from OUT0 to OUT31)
0:
Clear Output (Set 0)
1:
Force Output (Set 1)
0x44
(68)
1..32
R
Output Switching
Counts
U32
{0,0…}
N
Count the number of
switching times of each
output. The count value is
saved
3
every hour, or
automatically
4
in the SI unit
when the IO-Link power is
turned off.
When the counter reaches
the maximum value
4,294,967,295, this value is
retained and it does not
return to zero.
0x56
(86)
1,2,3,4
R/W
Output Open
Circuit Detection
U8
{0,0,0,0}
Y
Enable / disable Output
Open Circuit Detection
(individual setting from
OUT0 to OUT31)
0:
disable
1:
enable
0x57
(87)
1,2,3,4
R
Output Open
Circuit Status
U8
{0,0,0,0}
N
Output status for open
circuit
(individual status from
OUT0 to OUT31)
0:
normal
1:
open circuit