Structure of Output Open Circuit Detection Parameter (index 86)
Determine enable/disable of the open circuit detecting function of each output (output 0 to output 31) by
four 8-bit long sub-index.
Bit 0 in the bit field corresponds to Output 0, Bit 1 to Output 1 and so on.
An example of setting is shown below.
Output Open Circuit Detection
Sub-Index
Output
Output Open Circuit Detection
Bit No.
Value
7
6
5
4
3
2
1
0
1
0-7
All disable
Output No.
-
7
6
5
4
3
2
1
0
Setting value
00
0
0
0
0
0
0
0
0
2
8-15
All enable
Output No.
-
15 14 13 12 11 10 9
8
Setting value
FF
1
1
1
1
1
1
1
1
3
16-23
All disable
Output No.
-
23 22 21 20 19 18 17 16
Setting value
00
0
0
0
0
0
0
0
0
4
24-31
Output 24-27: Disable
Output 28-31: Enable
Output No.
-
31 30 29 28 27 26 25 24
Setting value
F0
1
1
1
1
0
0
0
0
Structure of Output Open Circuit Status Parameter (index 87)
The output status for open circuit of each output (output 0 to output 31) is indicated by four 8-bit long sub
index.
An example of status is shown below.
Output Open Circuit Status
Sub-Index
Output
Output Open Circuit Status
Bit No.
Value
7
6
5
4
3
2
1
0
1
0-7
All output normal
Output No.
-
7
6
5
4
3
2
1
0
Status value
00
0
0
0
0
0
0
0
0
2
8-15
All output open circuit
Output No.
-
15 14 13 12 11 10 9
8
Status value
FF
1
1
1
1
1
1
1
1
3
16-23
All output normal
Output No.
-
23 22 21 20 19 18 17 16
Status value
00
0
0
0
0
0
0
0
0
4
24-31
Output 24-27: Output normal
Output 28-31: Output open circuit
Output No.
-
31 30 29 28 27 26 25 24
Status value
F0
1
1
1
1
0
0
0
0
Structure of Output Short Circuit Status Parameter (index 88)
The output status for short circuit of each output (output 0 to output 31) is indicated by four 8-bit long sub
index.
An example of status is shown below.
Output Short Circuit Status
Sub-Index
Output
Output Short Circuit Status
Bit No.
Value
7
6
5
4
3
2
1
0
1
0-7
All output normal
Output No.
-
7
6
5
4
3
2
1
0
Status value
00
0
0
0
0
0
0
0
0
2
8-15
All output short circuit
Output No.
-
15 14 13 12 11 10 9
8
Status value
FF
1
1
1
1
1
1
1
1
3
16-23
All output normal
Output No.
-
23 22 21 20 19 18 17 16
Status value
00
0
0
0
0
0
0
0
0
4
24-31
Output 24-27: Output normal
Output 28-31: Output short circuit
Output No.
-
31 30 29 28 27 26 25 24
Status value
F0
1
1
1
1
0
0
0
0