-18-
No.EX
※※
-OMX1001
1: Remote control (IP Address X switch set to 000)
The mode to respond to the following commands of the BOOTP/DHCP Server, supplied by Rockwell Automation.
When receiving the IP address from the BOOTP/DHCP Server, please check the following points:
•The communication cable is not connected to the master unit.
•Power is not supplied to the master unit.
Enable DHCP
The IP address etc. can be obtained from the BOOTP/DHCP Server. If the power supply is switched off and on again in this state,
the SI unit will obtain the IP address etc. again.
Disable BOOTP/DHCP
The IP address etc. cannot be obtained from the BOOTP/DHCP Server. If the power supply is switched off and on again in this state,
the previous settings will be maintained.
2: DHCP mode (IP Address X switch set to 255)
The mode to obtain the IP address from the DHCP server. The IP address will be lost when the power supply is turned off.
When receiving the IP address from the BOOTP/DHCP Server, please check the following points:
•The communication cable is not connected to the master unit.
•Power is not supplied to the master unit.
3: Manual setting of IP address
Manual setting of the IP address within the range 192.168.0.1 to 254, or 192.168.1.1 to 254.
Default setting
The default settings are "Remote Control" and "Enable DHCP" mode.
NOTE
In Remote Control mode, if the EX260 IP address is unknown, change to DHCP mode and
re-assign the correct IP address. When the DHCP server has assigned the correct address, turn off
the power supply and return the unit to Remote control mode.
Upon power-up, the EX260 will now be available using the address that was set whilst in DHCP
mode.