Alarm indication and remedy

Perform the following remedy when an alarm comes out.

Point

Display

Content

Disposition

Emergency stop

Emergency stop input is
opened or power supply
for signal is cut off.

Confirm the power supply
for signal is energized and
release emergency stop
input.

3 positions : See the circuit on page 13.
5 positions : See the circuit on page 25.

Abnormal external
output

Abnormal external output.

Alarm signal is not out-
put.

[Common power supply]
Turn off power supply
once to check the wiring
condition of load and mod-
ify it if necessary. Then
reapply the power supply.

3 positions : See the circuit on page 13.
5 positions : See the circuit on page 25.

[Independent power supply]
Turn off power supply for
signal once to check the
wiring condition of load
and modify it if necessary.
Then reapply the power
supply and push MIDDLE
button.

3 positions : See the circuit on page 13.
5 positions : See the circuit on page 25.

Common Functions (continue)

Abnormal power
supply

Power supply voltage is
excessive or lower than
limit for operation.

Check the voltage and
adjust it if necessary and
then perform alarm reset.

Point

Display

Content

Disposition

Abnormal 
temperature

Internal temperature of
controller becomes exces-
sive.

Decrease ambient temper-
ature of the actuator and
then perform alarm reset.

Abnormal drive

Max. output is continued
for prolonged period.

Check the weight of work
and foreign material
attached to actuating part
and then perform alarm
reset.

Tuming off

Ligting

blink

Abnormal stroke

The motor is revolving at
excessive speed or stops
before target stroke is
achieved.

I f   f o r e i g n   m a t e r i a l   i s
f o u n d ,   r e m o v e   i t   a n d
then perform alarm reset.

Abnormality of
motor

The motor does not revo-
lute properly or over cur-
rent is detected.

Perform alarm reset.

When controller separate
type is used, check con-
nected part between
motor and controller after
turning off the power sup-
ply.

Readjust stroke adjust-
i n g   u n i t   t o   t h e   g i v e n
s t r o k e   a n d   p e r f o r m
s t r o k e   l e a r n i n g   a g a i n
a f t e r   t u r n i n g   o f f   t h e
power supply.   Note 1)

When controller separate
type is used, check con-
nected part between
motor and controller after
turning off the power sup-
ply.

Note 1): The product is in the condition same as after stoke learning is completed. The actuator does not

return to original position by the first input of drive command.

•If the error can not be released, turn off power supply, stop use of the product and contact SMC sales

responsibility.

Abnormality of 
controller

CPU is running way out of
control or the content of
memory is abnormal.

Turn off power supply
once and then turn it on
again.

Abnormality of 
setting value

Setting switch of speed
and acceleration is
changed under locked
condition.

Return setting value of
speed and acceleration to
the one at the lock condi-
tion (See page 35 Lock
function).

Alarm signal is not out-
put.

(

)

(

)

(

)

Summary of Contents for E-MY2B Series

Page 1: ...e Rodless Actuator E MY2B Series Operation Manual URL http www smcworld com...

Page 2: ...FINLAND 358 9 859 580 PORTUGAL 351 2 610 89 22 FRANCE 33 1 64 76 1000 SPAIN 34 945 18 4100 GERMANY 49 6103 4020 SWEDEN 46 8 603 0700 GREECE 30 1 342 6076 SWITZERLAND 41 52 396 3131 HUNGARY 36 1 371 13...

Page 3: ...injury Do not disassemble remodel including change of printed circuit board or repair An injury or failure can result Do not operate beyond specification range Fire malfunction or switch damage can re...

Page 4: ...t use in the environment subject to temperature cycle Do not use where close to surge generating source Do not short the load Short of the load of the controller is indicated as error but it may cause...

Page 5: ...controller Encoder cable of the actuator Motor cable of the actuator Controller separated type Installation Read Precautions for Handling of safety Instruction and How to install of this chapter with...

Page 6: ...rail While pushing it fix it by the clamp of screw in fig 4 Inadequate pushing may cause falling of parts Direct mounting Use M4 mounting screw shown in fig 1 or M5 tap hole to mount the controller Ho...

Page 7: ...t light goes out blink lighting No Content Function Stroke learning switch The switch to move the actuator to intermediate position and set the intermediate position The switch to move the work to mot...

Page 8: ...bnormal stroke Abnormality of motor Abnormality of controller Abnormal detection items Current consumption Current consumption DC24V 10 30mA output load capacity at DC24V Power supply voltage Symbol C...

Page 9: ...g OUT2 OUT3 Symbol Command IN1 Command to operate motor side Command to operate end side Command to operate intermediate stop IN2 Symbol Connection of the motor and the controller When controller sepa...

Page 10: ...ps MOTOR and END are blinking Since the actuator starts moving automatically to learn the adjusted stroke do not put any objection such as tool and work around the actuator 3 3 After stroke learning i...

Page 11: ...stment of switch and the speed of actuator is set Rotary switch to set speed of movement to the direction of the motor side Rotary switch to set speed of movement to the direction of the end side 6 2...

Page 12: ...ce Noise resistance Between external terminal and case 50 M 500 VDC 1000 Vp p Pulse width 1 s Rise time 1 ns Acquired certified standard CE marking Item Specification Transfer acceleration set range M...

Page 13: ...MIDDLE indicator lamp Green MOTOR indicator lamp Green END indicator lamp Green PWR indicator lamp Green ALM indicator lamp Red Power is turn on Symbol When positioning completed External input stop c...

Page 14: ...y of motor Abnormality of controller Abnormal detection items Current consumption Current consumption DC24V 10 30mA output load capacity at DC24V Power supply voltage Symbol Cable color Signal name Co...

Page 15: ...IN1 Command to operate motor side Command to operate end side Command to operate intermediate stop 1 Command to operate intermediate stop 2 Command to operate intermediate stop 3 External input stop c...

Page 16: ...tor lamp of MIDDLE MOTOR and END blink for max 3s When intermediate position is not set position 1 to 3 are all set at the center of the stroke Press again within 3s after pressing Press within 3s aft...

Page 17: ...r side is moved the intermediate position is changed On the other hand change of the position of the stroke adjusting unit at stroke does not make sense If the stroke is set shorter than the distance...

Page 18: ...not turn off input of drive command until READY output is confirmed The signal for completion of positioning is output when the actuator reaches the position 0 5mm before target position indicated as...

Page 19: ...00 to 1000 mm s Acceleration and deceleration method Trapezoidal drive Moving direction Horizontal direction Positioning points Both ends mechanical stoppers 3 intermediate position Intermediate stopp...

Page 20: ...m alarm reset Abnormal drive Max output is continued for prolonged period Check the weight of work and foreign material attached to actuating part and then perform alarm reset Tuming off Ligting blink...

Page 21: ...om alarm condition Alarm output Longer than 50ms Emergency stop input READY output contact is opened External alarm reset Even if alarm occurs it recovers from alarm condition by inputting emergency s...

Reviews: