Parameter description: The safety
program in the system will memorize the
water inlet and outlet speed during
calibration. During the water change task,
if the inlet and outlet speed changes a lot,
it may cause a timeout alarm.
1
2
3
·
Project location:
F1S5
Option On: Turn on temperature linkage during
water change
· Default: Off
Option Off: Disable temperature linkage during
water change
· You can set the minimum temperature limit when
changing water. The system will be suspended
below this temperature, and the process will
resume automatically when the temperature
recovers and 1 ° above this set value.
·
Project location:
F1S5-On-LXXX
4
·
Project location:
F1S5-On-HXXX
· You can set the maximum temperature limit when
changing water. The system will be suspended
above this temperature, and the process will
resume automatically when the temperature is
restored and 1 ° below this set value.
Low limit
Timeout
parameter
Temperature
linkage
Advanced settings (optional) [S1 -AWC]
Hight limit
5
Increasing the value of this parameter can
increase the system's response to water inlet
and outlet Tolerance of speed change.
11
Timeout
parameter
6
1
2
3
·
Project location:
F2S1
· After entering this setting, the system starts
to add water, please press the set button again
when the water level rises about 5-7MM to
end the setting. From now on,A.T.O. function
will raise the water level by 5-7MM each time.
·
Project location:
F1S6-XXX
· Modify tolerance in order: water in, water
out, and simultaneously.
· Default: 200% / 100% / 150%
· Do not modify this item unless necessary.
· It can set the maximum running times of
A.T.O. function within 24 hours. Once this
number is exceeded, the system will
automatically stop and alarm.
·
Project location:
F2S3-XXX
· Default: 50 times
4
·
Click the Pause button during standby to pause
the ATO function. At this time, if the water level is
lowered below the LOW sensing point, the water
level will not be automatically restored. You can
click the ATO button to start one-key top-up at a
time. There is no time limit for the top-up process.
Set the amount
of A.T.O.
· This function is used to prevent the pump from
running dry when water is scarce. If the number of
consecutive water additions exceeds the value
while the A.T.O. function is running and the water
level is still too low, the system will stop the alarm.
·
Project location:
F2S3-XX
12
Advanced settings (optional) [S2 -A.T.O.]
Limit on the
number of runs
Limits on the
number of
failures
One-click
top up
Timeout
parameter