Controller for single actuator (side shift, tilt of yoke, telescopic arm)
(The illustration is from side shift controller. The procedure is the same for tilt and telescoping)
No reaction on actuator for side shift,
tilt of yoke or telescopic arm.
Voltage must be + 24 Volt
(Clamp 1 and 4)
Security switch can be disconnected.
Voltage must be + 24 Volt between
Clamps 1 and 6 as between 1 and 7
Fault on remote control when moving
single actuators
Voltage must be + 24 Volt between
clamps 1 and 9 as between 1 and 10
Activate the control panel for
movement of tilt, side shift or
telescopic arm.
Voltage between clamps 2 and 3 must
be 24 Volt or more
No reaction on movements and none
of the above faults.
Voltage between clamp 8 and 14 must
be + 5 Volt
If this is not the case, the print on the
controller can be defective
3. Stop-Down at Drive Section
Clamp 1 and 4
Clamp 1 and 6
Clamp 1 and 7
Clamp 1 and 9
Clamp 1 and 10
Clamp 2 and 3
Clamp 8 and 14