HMC9000 Diesel Engine Controller User Manual
HMC9000 Diesel Engine Controller 2015-12-25 Version 1.3 Page 40 of 52
Icon
No.
Function
Cable Size
Description
Break wire protection function is fitted
(Configurable).
13
Aux. output 4(D)
1.5mm
2
DC power is supplied by 7 terminal, rated 7A.
14
Aux. output 5(E)
1.5mm
2
DC power is supplied by 7 terminal, rated 7A.
15
Aux. output 6(F)
1.5mm
2
Volts Free; Rated current: 7A
16
17
18
MP1
(Magnetic
)
1.0mm
2
Speed sensor input.
19
MP2
(Magnetic
pickup-)
1.0mm
2
D+
20
D+ Charge input
1.0mm
2
Charging generator D+ terminal input; Ground
connected is not allowed.
21
AUX. input 1(A)
1.0mm
2
Digital input; Break wire protection function is
fitted (Configurable).
22
AUX. input 2(B)
1.0mm
2
Digital input; Break wire protection function is
fitted (Configurable).
23
AUX. input 3(C)
1.0mm
2
Digital input; Break wire protection function is
fitted (Configurable).
24
AUX. input 4(D)
1.0mm
2
Digital input; Break wire protection function is
fitted (Configurable).
25
AUX. input 5(E)
1.0mm
2
Digital input; Break wire protection function is
fitted (Configurable).
26
AUX. input 6(F)
1.0mm
2
Digital input; Break wire protection function is
fitted (Configurable).
27
COM(B-)
1.0mm
2
CANBUS
(EXPAN-
SION)
28
SCR (EXPANSION)
0.5mm
2
For ECU module and expansion module
connection.
Impedance-120
Ω
shielding
wire
is
recommended, its single-end earthed.
There is 120Ω terminal resistance inside
already; if needed, make terminal 30, 31 short
circuits. (HCM9000E without)
29
CAN(H) (EXPANSION)
30
CAN(L) (EXPANSION)
31
120
Ω
CANBUS
(REMOTE)
32
SCR
(REMOTE)
0.5mm
2
For remote control module connection.
Impedance-
120Ω
shielding
wire
is
recommended, its single-end earthed.
There is 120Ω terminal resistance inside
already; if needed, make terminal 34, 35 short
circuits.
33
CAN(H)
(REMOTE)
34
CAN(L)
(REMOTE)
35
120
Ω
36
Aux. output 7 (G)
0.5mm
2
B+ voltage output, rated current is 0.5A.
37
Aux. output 8 (H)
0.5mm
2
B+ voltage output, rated current is 0.5A.