9 INPUT/OUTPUT PORTS CONFIGURATION
9.1 AUXILIARY INPUTS 1~18 FUNCTIONAL CONFIGURATION
9.1.1 Digital Input Port Configuration
No.
Settings
Contents
Description
1
Feature Set
(0-50)
See
8.1.2 INPUT PORT FUNCTIONS
2
Active type
(0-1)
0: Close to activate
1: Open to activate
3
Arming
(0-3)
0: From Safety on
1: From Crank
2: Always
3: Never
4
Active action
(0-4)
0: Warn
1: Shutdown
2: Indication
5
Input Delay
(0-20.0)s
6
Open Check Enable
(0-1)
0:Disabled 1:Enable Only input ports
1~6 and speed input have this function.
7
Display string
User-defined input port
names
20 English symbols or 10 Chinese
characters
9.1.2 Input Ports Functions
No.
Function
Description
0
Not used
1
User-defined
Users configured input port settings
2
Alarm Mute
Can prohibit “Audible Alarm” output when input is active.
3
Reset alarm
Can reset all alarms when input is active.
4
Raise Speed
The generator will increase speed by GOV when the input is active.
5
Drop Speed
The generator will decrease speed by GOV when the input is active.
6
Reserved
7
Reserved
8
Lamp test
All LED indicators are illuminating when input is active.
9
Local mode in
Local mode is activated when input is active.
10
Remote mode in
Remote mode is activated when input is active.
11
Remote start
Automatically starts the generator in remote mode when the input is
active. Only the active shutdown input will be able to stop the
generator. (Inch or hold the button for more than 1s)
12
Remote stop
Stops the generator in remote mode when the input is active.
13
Remote start/stop
Automatically starts the generator in remote mode; the generator will
shut down when this input is deactivated.
14
Pre-lubricate
If output is set as pre-lubrication output, the relay disconnects after
the set pre-lubrication delay.