background image

                                                      HMC9000 Diesel Engine Controller User Manual   

HMC9000 Diesel Engine Controller                    2015-12-25                    Version 1.3                Page 27 of 52

 

15 

Override mode in 

Override mode is activated when the input is active; in override mode 

only  overspeed  shutdown  and  emergency  shutdown  will  stop  the 

engine.   

16 

Emergency stop 

The  controller  shuts  down  the  engine  immediately  and  records 

occurrence time. 

17 

Panel lock 

All  buttons  in  panel  is  inactive  except 

  and 

there is 

  in the left of first row in LCD when input is active. 

18 

Reserved 

 

19 

Power Change 

Transfers from main battery to standby battery. 

20 

Raise Speed Aid 

Raise speed relay will disconnect when the input is active. 

21 

Reserved 

 

22 

Drop Speed Aid 

Drop speed relay will disconnect when the input is active. 

23 

Water 

Heating 

feedback 

The  feedback  signal  of  water  heating  output;  The  screen  displays 

Water Heating feedback 

when the input is active.

 

 

24 

Pre-lube feedback 

The feedback signal of Pre-lube output; The screen displays

 Pre-lube 

feedback 

when the input is active. 

25 

Charging feedback 

The  feedback  signal  of  Charging  output;  The  screen  displays

 

Charging feedback 

when the input is active. 

26 

Reserved 

 

27 

Reserved 

 

28 

Quick start   

Cranking  will  start  directly  (without  preheating)  when  the  input  is 

active. 

29 

Reserved 

 

30 

60Hz Select 

Frequency selection of ECU engine   

31 

Turning Chain 

Start inhibition when the input is active. 

32 

Clean Cylinder   

Start relay outputs when clean cylinder input is active. 

33 

Reserved 

Reserved 

34 

Self-check 

Alarms can test with no rotated speed when self-check input is active. 

35-50 

Reserved 

 

Note:

 The name of the input ports 1~18 only can be configured via PC software.

 

 

 

 

 

 

 

Summary of Contents for HMC9000

Page 1: ...1 HMC9000 DIESEL ENGINE CONTROLLER With J1939 Interface USER MANUAL ZHENGZHOU SMARTGEN TECHNOLOGY CO LTD...

Page 2: ...rt Auxiliary Relay Output 2 7 A Connect to common output port Auxiliary Relay Output 3 7 A Connect to common output port Auxiliary Relay Output 4 7 A Connect to common output port Auxiliary Relay Outp...

Page 3: ...All alarm only can be removed after reset Lamp Test Press this button will test panel LED indicators and display screen Mute Alarm sound off Up Increase Screen scroll Up cursor and increase value in s...

Page 4: ...rrent type main battery voltage standby battery voltage charger voltage total running time total start times and GOV output percentage Note sensor names are user set If J1939 is enabled the following...

Page 5: ...2 Alarm Mute Can prohibit Audible Alarm output when input is active 3 Reset alarm Can reset all alarms when input is active 4 Raise Speed The generator will increase speed by GOV when the input is act...

Page 6: ...the input is active 23 Water Heating feedback The feedback signal of water heating output The screen displays Water Heating feedback when the input is active 24 Pre lube feedback The feedback signal...

Page 7: ...mm2 Battery 1 voltage input 4 B1 input 2 5mm2 5 B2 input 2 5mm2 Battery 2 voltage input 6 B2 input 2 5mm2 7 COM Relay 2 5mm2 Common relay power supply input 8 Fuel relay 2 5mm2 DC power is supplied by...

Page 8: ...ion is fitted Configurable 24 AUX input 4 D 1 0mm2 Digital input Break wire protection function is fitted Configurable 25 AUX input 5 E 1 0mm2 Digital input Break wire protection function is fitted Co...

Page 9: ...2 Aux input 15 O 1 0mm2 Digital input 53 Aux input 16 P 1 0mm2 Digital input 54 Aux input 17 Q 1 0mm2 Digital input 55 Aux input 18 R 1 0mm2 Digital input 56 COM B input 1 0mm2 57 AIN1 A 1 0mm2 Resist...

Page 10: ...sion 1 3 Page 42 of 52 11 TYPICAL WIRING DIAGRAM HMC9000 Typical Wiring Diagram Note 1 Power supply for fuel relay start relay and auxiliary outputs 1 5 are supplied by terminal 7 2 To activate batter...

Page 11: ...if you connect external device with current lower than 0 5A it can be connected directly 2 Controller expansion modules can only be used together with the main controller however the main controller c...

Page 12: ...he help of PC or DAS Data Acquisition Systems operational software provides a simple and useful marine engine monitoring system management scheme and enables remote control remote measurement and remo...

Page 13: ...gine 8 pin terminal 4 wire and 5 wire Set auxiliary output 2 as Preheating until cranking and set preheating time as 5 seconds 3 Power supply negative 4 Power supply positive SCR EXPANSION CAN communi...

Page 14: ...mute and other functions to be performed on the distance All engine parameters and real time events are displayed on the remote control module Note Remote control module can only be used in remote mo...

Reviews: