HGM1780
Automatic
Genset Controller
ISSUE 2013-04-03
Version1.7
Page 16 of 24
HGM1780 Automatic Genset Controller
No.
Parameter
Range
Default
value
Description
P35
Module
Address
(1-254)
1
Communication address
P36
Crank
Disconnect
Condition
(0-5)
See table 5.
1
Starter
motor
disconnection
condition. There are 3 conditions of
disconnecting starter with engine.
Each condition can be used alone
and simultaneously to separating
the start motor and genset as soon
as possible.
P37
Disconnect
Engine
Speed
(0-3000) RPM
360
When generator speed higher than
the set value, starter will be
disconnected.
P38
Disconnect
Generator
Freq
(10-30) Hz
14.0
When generator frequency higher
than the set value, starter will be
disconnected.
P39
Disconnect
Oil Pressure
(0-400) kPa
200
When generator oil pressure higher
than the set value, starter will be
disconnected.
P40
Temperature
Sensor
(0-10)
06
SGD (120ºC resistor type)
P41
Oil Pressure
Sensor
(0-10)
06
SGD (10Bar resistor type)
P42
Fuel
Level
Sensor
(0-7)
0
Not used. (If fuel level sensor is
used, then the digital input port
must be set as „not used‟.
P43
Over Current
Action
(0-2)
0
0: Warn; 1: Shutdown; 2:Trip