HGM1780 

Automatic 

Genset Controller 

ISSUE 2013-04-03 

Version1.7 

Page 8 of 24 

HGM1780 Automatic Genset Controller 

 

 

4.2. LCD ICONS 

4.  OPERATION 

4.1. PANEL KEYS 

 

Key 

Definition 

Description 

 

 

 

 

 

 

Manual/Decrease 

Pressing  this  button  will  start  the  generator 
manually  and  place  it  into  its  manual  mode;  in 
settings  menu  moves  cursor  down  and  decreases 
the set value. 

 

 

Auto/Increase 

Pressing  this  button  will  place  the  module  into  its 
auto mode; in settings menu moves cursor up and 
increases the set value. 

 

 

Stop 

Pressing this button in any situation will shut down 
the generator and place it into its standby mode; in 
case of alarm, pressing this button will clear alarms. 

 

Turn Page 
/Confirm 

Using this button you can scroll pages of  the LCD 
monitor; in settings menu press to move cursor and 
confirm. 

 

Alarm Indicator 

This indicator will flash when an alarm occurs. 

 

 

Icon 

Definition 

Icon 

Definition 

 

High Temp. Alarm 

 

Auto Mode 

 

Low Oil Pressure 

 

Stop Mode 

 

Over Speed Alarm 

 

Manual Mode 

 

Under Speed Alarm 

 

Gens Volts Indication 

 

Emergency Stop 

 

Battery Volts Indication 

 

Over Voltage 

 

Speed Unit (Per Minute) 

 

Under Voltage 

 

Oil Pressure Unit 

 

Fail to start 

 

Voltage Unit 

 

Fail to stop 

 

Fuel Level Unit (%) 

 

Voltage Abnormal 

 

Temperature Unit 

 

 

Auxiliary Alarm 

 

 

Frequency Unit 

 

 

Normal Run 

 

 

Hours Count 

 

 

Fuel Level Low 

Load Current 

Summary of Contents for HGM1780

Page 1: ...USER MANUAL HGM1780 Automatic Genset Controller Smartgen Technology...

Page 2: ...AY DESCRIPTION 9 4 4 OPERATION INSTRUCTION 9 5 PROTECTION 12 6 PARAMETER RANGE AND DEFINITION 13 6 1 PARAMETERS CONFIGURATION TABLE 1 13 6 2 DEFINITION OF RELAY OUTPUTS TABLE 2 17 6 3 DEFINITION OF DI...

Page 3: ...th 3 working modes that can be selected from the front panel It can detect one phase generator voltage and current can be started and stopped manually or via a remote start stop signals In case of fau...

Page 4: ...enerator frequency Hz Generator current A Engine temperature C Oil pressure kPa Engine speed rpm Total running time H Battery voltage V Fuel level Generator voltage battery voltage engine speed temper...

Page 5: ...uts fuel relay start relay 1 configurable output port which can be set as common alarm output fail to stop output preheat output or idle control output Parameters can be set and modified by users and...

Page 6: ...changes every six minutes Start Relay Output 1Amp DC28V DC B power supply Fuel Relay Output 1Amp DC28V DC B power supply Programmable Relay Output 1Amp DC28V DC B power supply Digital Input Active whe...

Page 7: ...ut down the generator and place it into its standby mode in case of alarm pressing this button will clear alarms Turn Page Confirm Using this button you can scroll pages of the LCD monitor in settings...

Page 8: ...preheat delay begins One second before it is finished fuel output will 4 3 DISPLAY DESCRIPTION Generator phase voltage Ua frequency F Loading current la engine speed Oil pressure water temperature Liq...

Page 9: ...seconds after the beginning of the delay preheat and ETS outputs will be activated after the end of the delay ETS output will be deactivated and fuel relay output preheat output will be deactivated be...

Page 10: ...nly react to emergency stop signal Note Configurable output ports can be set as one of the following functions ETS output Idle output or Preheat output via PC Therefore all three functions can not be...

Page 11: ...ry voltage warning signal is sent Only warning and not shutdown 9 Low Battery Voltage if battery voltage stays below the pre set value for 20 seconds low battery voltage warning signal is sent Only wa...

Page 12: ...il P06 Safety On Delay 1 60 s 10 Alarms for low oil pressure high temperature under speed under frequency voltage charge fail are inactive P07 Start Idle Time 0 3600 s 0 Idle running time of genset wh...

Page 13: ...speed falls below this value and stays so for 10 seconds this is regarded as under speed and under speed alarm shutdown signal is sent P19 Engine Over Speed 0 6000 RPM 1710 When engine speed exceeds...

Page 14: ...attery Over Volts 12 40 V 33 0 When battery voltage exceeds this value and stays so for 20 seconds Battery Over Volts signal is send and warning without shutdown is initiated P27 Battery Under Volts 4...

Page 15: ...ossible P37 Disconnect Engine Speed 0 3000 RPM 360 When generator speed higher than the set value starter will be disconnected P38 Disconnect Generator Freq 10 30 Hz 14 0 When generator frequency high...

Page 16: ...isconnects after complete stop 4 Preheat control It closes before starting and opens before starter is power on 5 Closing Gens During normal operation of the generator closes the breaker 6 Reserved No...

Page 17: ...Dongkang sensor 7 CURTIS 8 DATCON 10Bar 9 VOLVO EC 10 SGX 10Bar Digital closed and Digital open both are digital signal low or high electrical level can be selected to be active connecting to earth p...

Page 18: ...er motor as soon as possible 2 Magnetic pickup is the magnetic equipment which be installed in starter for detecting flywheel teeth 3 When set as magnetic pickup must ensure that the number of flywhee...

Page 19: ...y that is used for password to enter the set value Password Parameter Setting Attention 1 Please change the controller parameters when generator is in standby mode only e g Crank disconnect conditions...

Page 20: ...rk 2 If the generator is in manual mode and crank disconnect condition is set as 2 magnetic pickup generator frequency or 5 generator frequency magnetic pickup oil pressure and generator frequency and...

Page 21: ...onfigurable Input Configurable input port can be configured as digital signal or fuel level sensor signal digital input active when connected to B Terminal 8 Oil Pressure Input Low oil pressure or sen...

Page 22: ...HGM1780 Automatic Genset Controller ISSUE 2013 04 03 Version1 7 Page 23 of 24 HGM1780 Automatic Genset Controller 9 OVERALL DIMENSIONS PANEL CUTOUT 78MMX66MM...

Page 23: ...HGM1780 Automatic Genset Controller ISSUE 2013 04 03 Version1 7 Page 24 of 24 HGM1780 Automatic Genset Controller 10 TYPICAL APPLICATION...

Reviews: