HEM8500 Engine CAN Monitoring Controller User Manual Page 26 of 45
No.
Items
Parameters
Defaults
Description
Speed
adjusted.
10 Throttle Resolution 0~100 r/min
50
Resolution of the throttle knob each turn of
a grid.
11
SPN Alarm Mask
Code 1
(0~65535)
0
It is can shield corresponding SPN alarm.
12
SPN Alarm Mask
Code 2
(0~65535)
0
It is can shield corresponding SPN alarm.
13
SPN Alarm Mask
Code 3
(0~65535)
0
It is can shield corresponding SPN alarm.
14
ECU Comm. Failure
Action
(0~1)
0
0: Warning; 1: Shutdown
15 Alt. Config. 1 Speed (0~3000)r/min
1500
Alt. configuration 1 speed associated with
alt. configuration 1 of input port.
16 Alt. Config. 2 Speed (0~3000)r/min
1500
Alt. configuration 2 speed associated with
alt. configuration 2 of input port.
17 Alt. Config. 3 Speed (0~3000)r/min
1500
Alt. configuration 3 speed associated with
alt. configuration 3 of input port.
18 External Crank Set
(0-1)
0
0: Disable; 1: Enable
19
ECU
Comm.
Address
(0-255)
7
It is used for setting ECU communication
address.
20
Shutdown
Alarm
Inhibition
(0-1)
1
0: Disable; 1: Enable
When it enables, only emergency stop and
emergency shutdown of input port can stop.
21 Speed control step
(0~1000)r
266
The step length of each increasing speed.
22
Speed Control
Slope
(0~1000)r/s
100
The increasing number of speed per
second.
23
RP Speed Control
Enable
(0-1)
0
0: Disable; 1: Enable
When
the
speed
adjustment
of
potentiometer enables and the throttle
switch is active to realize potentiometer
speed regulation.
24 RP Start Resistance (0~5000) Ω
0
The
Initial
resistance
value
of
potentiometer.
25 RP Max. Resistance (0~5000) Ω
1000
The max. resistance value of potentiometer.
26 RP Sensor Select
(0~2)
0
0: Not Used;
1: Flexible Sensor 1;
2: Flexible Sensor 2.
Module Setting
1
Module Address
(1~254)
1
It is used for setting RS485 communication
address.
2
Language
(0~2)
0
0: Simplified Chinese
1: English