HAT162 ATS Controller User Manual Page 12 of 21
NOTE:
a)
The parameters in this form can be set via computers and slave;
b)
When delay is “7: User defined”, parameter delay must be set via computer. If parameter is not set via computer, the
delay is Default; if parameter has been set via computer, then the delay is the set value.
Table 7 Parameters Definition and Range Table (2)
No.
Item
Range
Default
Description
1
Rated Voltage
(170-270)V
230
Provide base for over/under volt judge.
2
Rated Frequency
(50.0-60.0)Hz 50.0
Provide base for over/under frequency judge.
3
Over Voltage Warn
(0-1)
1
0: Disabled 1: Enabled
4
Over Volt Set Value
(100-120)%
115
Threshold value
5
Over Volt Return Value (100-120)%
113
Return value
6
Under Voltage Warn
(0-1)
1
0: Disabled 1: Enabled
7
Under Volt Set Value
(70-100)%
75
Threshold value
8
Under
Volt Return
Value
(70-100)%
77
Return value
9
Over Frequency Warn (0-1)
1
0: Disabled 1: Enabled
10
Over Freq. Set Value
(100-120)%
110
Threshold value
11
Over Freq. Return
Value
(100-120)%
104
Return value
12
Under Freq. Warn
(0-1)
1
0: Disabled 1: Enabled
13
Under Freq. Set Value (80-100)%
90
Threshold value
14
Under Freq. Return
Value
(80-100)%
96
Return value
15
Loss of Phase
(0-1)
1
0: Disabled 1: Enabled (fixed delay as 3s)
16
Reverse Phase Seq.
(0-1)
0
0: Disabled 1: Enabled (fixed delay as 3s)
17
Output Ports
(0-16)
0
0: Not Used
1: S1 Volts Normal
2: S1 Volts Abnormal
3: S2 Volts Normal
4: S2 Volts Abnormal
5: Manual Status Output
6: Auto Status Output
7: Gens Start Output(NO)
8: Gens Start Output(NC)
9: S1 Close Output
10: S2 Close Output
11: S1 Close Status Output
12: S2 Close Status Output
13: Reserved
14: Reserved
15: Reserved
16: Reserved
18
Module Address
(1-254)
1
Address that communicates with PC software.
NOTE:
The parameters in this form can be set via computers.