6.
WIRE CONNECTION
Fig.2 Controller Rear Panel Drawing
Table 5 Terminals Description
No.
Items
Function Description
Remark
1
N2
2# AC 3-phase 4-wire input
Single phase 2-wire: connect with A2 and N2,
B2 and C2 are not connected;
2-phase 3-wire: connect with A2, B2, and N2,
C2 is not connected;
3-phase 3-wire: connect with A2, B2, and C2,
N2 is not connected (special order required).
2
C2
3
B2
4
A2
5
N1
1# AC 3-phase 4-wire input
Single phase 2-wire: connect with A1 and N1,
B1 and C1 are not connected;
2-phase 3-wire: connect with A1, B1, and N1,
C1 is not connected;
3-phase 3-wire: connect with A1, B1, and C1,
N1 is not connected (special order required).
6
C1
7
B1
8
A1
9
1# Close Relay
Volt free normally open
contact output
Rated capacity: 16A/250VAC
10
11
2# Close Relay
Volt free normally open
contact output
Rated capacity: 16A/250VAC
12
13
Gen Start
Signal output
Volt free normally close
contact output
Rated capacity: 7A/250VAC
14
15
Aux. output
Volt free normally open
contact output
Rated capacity: 7A/250VAC
16
17
NC
Not connect