HAT162 ATS Controller User Manual Page 10 of 21
No.
Items
Function Description
Remark
18 1# Close Input
Detect 1# breaker close
status,
auxiliary
contact
input.
Ground is active.
19 2# Close Input
Detect 2# breaker close
status,
auxiliary
contact
input.
Ground is active.
20 Common Port
GND
LINK
Communication
Port
Communicate with PC and
used for program update
Used with SG72 adaptor.
F1
Fuse
Rated 10A 250V.
F2
Fuse
Rated 10A 250V.
7.
DEFINITION AND RANGE OF PARAMETERS
Table 6 Parameters Definition and Range Table (1)
No.
Items
Range
Default
Description
1
AC System
(1-4)
1
1: 3 Phase, 4 Wire (3P4W)
2: Single Phase, 2 Wire (1P2W)
3: 3 Phase, 3 Wire (3P3W) (special order required)
4: 2 Phase, 3 Wire (2P3W)
2
S1 Normal Delay
(1-7)
2
1: 1s
2: 5s
3: 10s
4: 20s
5: 30s
6: 45s
7: User defined (Default: 5s)
3
S2 Normal Delay
(1-7)
2
1: 1s
2: 5s
3: 10s
4: 20s
5: 30s
6: 45s
7: User defined (Default: 5s)
4
S1 Abnormal Delay
(1-7)
2
1: 1s
2: 5s
3: 10s
4: 20s
5: 30s
6: 45s
7: User defined (Default: 5s)
5
S2 Abnormal Delay
(1-7)
2
1: 1s
2: 5s