Configuration
3.15
Figure 3.11 - Transducer Configuration – User Table Screen
How to Configure the Analog Input Block
The Analog Input block takes the input data from the Transducer block, selected by channel
number, and makes it available to other function blocks at its output. The transducer block provides
the input unit of the Analog Input, and when the unit is changed in the transducer, the PV_SCALE
unit is changed too. Optionally, a filter may be applied in the process value signal, whose time
constant is PV_FTIME. Considering a step change to the input, this is the time in seconds to the PV
reaches 63.2 % of the final value. If the PV_FTIME value is zero, the filter is disabled. For more
details, please, see the Function Blocks Specifications.
To configure the Analog Input Block in offline mode, please, go to the main menu and select "Device
Offline Configuration - Analog Input Block. Using this window, the user can configure the block
mode operation, selects the channel, scales and unit for input and output value and the damping.
Summary of Contents for LD303
Page 1: ...Profibus PA Pressure Transmitter L D 3 0 3 M E...
Page 8: ...LD303 Operation and Maintenance Instruction Manual VIII...
Page 22: ...LD303 Operation and Maintenance Instruction Manual 1 14...
Page 26: ...LD303 Operation and Maintenance Instruction Manual 2 4...
Page 74: ...LD303 Operation and Maintenance Instruction Manual 4 6 Figure 4 4 Exploded View...
Page 83: ...Maintenance Procedures 4 15 Figure 4 8 TPE Software Screen...
Page 102: ...LD303 Certifications Information A 4 CSA NEMKO and EXAM CEPEL NEPSI...
Page 104: ...LD303 Certifications Information A 6 CEPEL...
Page 105: ...Appendix A A 7 Control Drawing Factory Mutual FM...
Page 106: ...LD303 Certifications Information A 8...
Page 108: ...LD303 Operation and Maintenance Instruction Manual B 2...