background image

FI303 - Operation and Maintenance Instruction Manual 

 

2.2 

Local Adjustment 

Two switches that are magnetically activated. They can be activated by the magnetic tool without 
mechanical or electrical contact. 
 

 

 

Figure 2.2 - LCD Indicator 

Summary of Contents for FI303

Page 1: ......

Page 2: ...web www smar com contactus asp www smar com Specifications and information are subject to change without notice Up to date address information is available on our website smar...

Page 3: ...costs Some of the advantages of bi directional digital communications are known from existing smart transmitter protocols Higher accuracy multi variable access remote configuration and diagnostics an...

Page 4: ...el are allowed to participate in the activities of mounting electrical connection startup and maintenance of the equipment Qualified personnel are understood to be the persons familiar with the mounti...

Page 5: ...ENT CONVERTER TRANSDUCER BLOCK PARAMETERS TABLE 3 4 CYCLIC CONFIGURATION 3 5 HOW TO CONFIGURE THE ANALOG OUTPUT BLOCK 3 9 CURRENT TRIM 3 12 VIA LOCAL ADJUSTMENT 3 16 TRANSDUCER DISPLAY CONFIGURATION 3...

Page 6: ...FI303 Operation and Maintenance Instruction Manual VI...

Page 7: ...ls of the output current Fieldbus 4 a 20 mA Start No Yes Is the indication correct See section 4 Maintenance OK Install the converter on the field following the instructions below Check the area class...

Page 8: ...FI303 Operation and Maintenance Instruction Manual VIII...

Page 9: ...cuit is protected by a humidity proof coating but frequent exposures to humidity may affect the protection provided It is also important to keep the covers tightened in place Every time they are remov...

Page 10: ...rminals one inside the cover and two externals located close to the conduit entries The FI303 uses the 31 25 kbit s voltage mode option for the physical signaling All other devices on the same bus mus...

Page 11: ...to the certification or specific standard for installation limitations Figure 1 4 Output Connections Avoid routing signal wiring close to power cables or switching equipment The FI303 is protected aga...

Page 12: ...ength A spur may connect more than one device depending on the length Active couplers may be used to extend spur length The total cable length including spurs between any two devices in the Fieldbus s...

Page 13: ...the Jumpers J1 This jumper enables the simulation mode parameter in the AO block W1 This jumper enables the local adjustment programming tree Table 1 1 Description of the Jumpers Power Supply The FI3...

Page 14: ...FI303 Operation and Maintenance Instruction Manual 1 6...

Page 15: ...ration of block execution self diagnostics and communication The program is stored in PROM For temporary storage of data there is a RAM The data in the RAM is lost if the power is switched off however...

Page 16: ...on and Maintenance Instruction Manual 2 2 Local Adjustment Two switches that are magnetically activated They can be activated by the magnetic tool without mechanical or electrical contact Figure 2 2 L...

Page 17: ...u Device option to configure the required parameters using the related menus NOTE It is not advisable to use the Download to Device option This function can misconfigure the equipment How to Configure...

Page 18: ...he final control element in units of OUT_SCALE Status BAD will indicate a hardware problem FINAL_VALUE_SCALE This is the output conversion of the linearisated value using the high and low scale The en...

Page 19: ...common to provide a plausibility check in the device The result of this check is indicated in the TAB_STATUS parameter 0 not initialised 1 good new table is valid 2 not monotonous increasing old tabl...

Page 20: ...for the device This is part of the Ordering Code information necessary to buy a spare unit Table 3 1 Parameters Description PROFIBUS to Current Converter Transducer Block Parameters Table Relative In...

Page 21: ...cyclic data exchange The FI303 has 3 functional blocks with analog output AOs that the class 1 master uses to execute the cyclic services and the user must choose what configuration best suits their a...

Page 22: ...de when detecting a communication loss between the slave and the master equipment Since the FI303 will be on a final element it is recommended that a fail safe value be configured The Simatic PDM Proc...

Page 23: ...ER TAB_MAX_NUMBER TAB_OP_CODE TAB_STATUS The TAB_X_Y_VALUE parameter contains the value couple of the each table entries The TAB_INDEX parameter identifies which element of the table is in the TAB_X_...

Page 24: ...is is useful for example when the FI303 is controlling a valve with a non linear characteristic Characterization curve when used is applied to the input signal before it is converted by the transducer...

Page 25: ...The Analog Output Block is a function block used by devices that work as output elements in a control loop like valves actuators positioners etc The AO block receives a signal from another function b...

Page 26: ...ion Selecting the page Scale Units the user has the option to configure the scale and unit for the input and output Figure 3 7 FI303 Simatic PDM Analog Output Block Scale Units Offline Configuration T...

Page 27: ...Offline Configuration In terms of Online configuration the user can select at the device menu the Online Configuration for each Analog Output block Figure 3 9 FI303 Simatic PDM Online Configuration mo...

Page 28: ...t The user can check the calibration of the transducer output by measuring the actual current in the output and compare it with the device s indication of course an appropriate meter should be used If...

Page 29: ...e have a new window that allows him to enter the desired value for the new calibrated point for the lower current Write for example 4 0mA in new value After entering the desired valve the generated cu...

Page 30: ...ated current is correct press No and a new warning appears After user confirmation the converter comes to the normal operation The upper calibration procedure is similar than the lower Figure 3 12 FI3...

Page 31: ...r example 20 0mA in new value After entering the desired valve the generated current is corrected according to the desired value and the user can make the correction until the right current is reached...

Page 32: ...ce it in orifice S Remove and reinsert the magnetic tool in S until the message Loc Adj is displayed The message will be displayed during approximately 5 sec after the user removes the magnetic tool f...

Page 33: ...lt Value Set 22 Out of range 26 Invalid Calibration request 27 Excessive Correction Transducer Display Configuration Using the Simatic PDM or any other configuration tool is possible to configure the...

Page 34: ...the magnetic tool it is necessary to previously prepare the parameters related with this operation via System Configuration There are six groups of parameters which may be pre configured by the user i...

Page 35: ...Configuration The Local Address Change window allows the user to enable disable the access to change the equipment address Figure 3 15 Parameters for Local Address Configuration When the user enter i...

Page 36: ...parameters at the same time it is only necessary to opt for none when configure the LCD II Figure 3 16 Parameters for Local Adjustment Configuration The user may select the Mode Block parameter on the...

Page 37: ...ics screw driver in span hole 4 Wait 3 seconds then MD will appear on display Browse Insert magnetic screw driver in zero hole and hold Select Insert magnetic screw driver in span hole and hold 1 HOW...

Page 38: ...ocedures Manual Please take a detailed look at this manual in the chapter related to Programming Using Local Adjustment It is significantly the resources on this transducer display also all the Series...

Page 39: ...justment Fig 3 19 J1 and W1 Jumpers Example let s say we want to calibrate the lower and upper current value From normal display enter local adjustment The display will show Figure 3 20 Step 1 FI303 M...

Page 40: ...ool in orifice S as soon as lower is shown on the display An arrow pointing upward increment the value and an arrow pointing downward decrement the value Apply the 4 00 mA current in the 1 and 4 termi...

Page 41: ...tion To implement the correction read the current measured on the Miliamperimeter and use the screwdriver to adjust the figure on the display to this value This option corrects the value of a lower ca...

Page 42: ...FI303 Operation and Maintenance Instruction Manual 3 26...

Page 43: ...he FI303 Fieldbus terminals must be between 9 and 32 VDC Electronics Circuit Failure Check circuit boards for defect by replacing them with spare ones NO COMMUNICATION Network Connection Check network...

Page 44: ...e factory Init use two magnetic screwdrivers Remove the screw on the equipment that fixes the identification tag on the carcass top to access the orifices bearing the letters S and Z The operations to...

Page 45: ...Reassembly Procedure Put output board 7 into housing 9 Anchor output board with its screws 6 Place the main plate 5 on the carcass and make sure the pins are connected Put display 4 into the housing...

Page 46: ...justment Protection Cap 10 204 0114 Identification Plate Fixing Screw 11 204 0116 Terminal Insulator 12 314 0123 External Ground Screw 13 204 0124 Housing in Aluminum 14 304 0119 Terminal Holding Scre...

Page 47: ...ation 185 F without damage Humidity Limits 0 to 100 RH Turn on Time Approximately 10 seconds Update Time Approximately 0 5 second Configuration Basic configuration may be done using local adjustment m...

Page 48: ...CONVERTER C D Local Indicator 0 1 Without Indicator With Digital Indicator C D Mounting Bracket for 2 Pipe Mounting 0 1 2 Without Bracket Carbon Steel Bracket 316 SST Bracket C D Electrical Connectio...

Page 49: ...DANCE TO APPROVAL LISTING 3 ASSOCIATED APPARATUS GROUND BUS TO BE INSULATED FROM PANELS AND MOUNTING ENCLOSURES 4 ASSOCIATED APPARATUS GROUND BUS RESISTANCE TO EARTH MUST BE SMALLER THAN 1 ONE OHM IF...

Page 50: ...FI303 Operation and Maintenance Manual 5 4...

Page 51: ...nterference presents in the area Without interference Temperature Vibration Others ______________________________ Ambient Temperature From __________ C up to __________ C OCCURRENCE DESCRIPTION ______...

Page 52: ...serial number and dispatch it to our factory For easier analysis and faster solution of the problem the returned material should include the documentation with a description of the failure observed i...

Page 53: ...operational limits temperature humidity etc according to the instructions manual In addition this Warranty Certificate excludes expenses with transportation freight insurance all of which are the cust...

Page 54: ...and SMAR and its dealer reserve themselves the right to refuse the service in cases not compliant to those conditions It is the customer s responsibility to tell SMAR and its dealer when the product w...

Reviews: