Configuration
3.17
For example, it is possible to enter 20.0 mA or the upper value. When the magnetic tool is removed
from “S”, the output will be adjusted to a value close to the desired value. The user should then
browse the tree up to parameter FEED (FEEDBACK_CAL) and actuate this parameter by placing
the magnetic tool in “S” until reaching the value shown by the multimeter.
The user should write in this parameter the multimeter readout value until 20.0 mA or the desired
upper values are displayed.
NOTE
Trim mode exit via local adjustment occurs automatically. Should the magnetic tool not be used
during some seconds.
LIMIT CONDITIONS FOR CALIBRATION
Lower
3.99 < NEW_LOWER < 11.5 mA, otherwise XD_ERROR = 22
Upper
12.50 < NEW_UPPER < 20.01 mA, otherwise XD_ERROR = 22
NOTE
Codes for XD_ERROR:
16
: Default Value Set
22
: Out of range
26
: Invalid Calibration request
27
: Excessive Correction
Transducer Display – Configuration
Using the
Simatic PDM or any other configuration tool
is possible to configure the Display
Transducer block. As the name described it is a transducer due the interfacing of its block with the
LCD hardware.
The Transducer Display is treated as a normal block by
any configuration tool
. It means, this block
has some parameters and those ones can be configured according to customer's needs.
The customer can choose up to six parameters to be shown at LCD display, they can be parameters
just for monitoring purpose or for acting locally in the field devices by using a magnetic tool. The
seventh parameter is used to access the physical device address. The user can change this
address according to his application. To access and configure the Display Block, please, go to the
main menu, select "Device OnLine Configuration - Display Block":
Figure 3.13 - Display Block and Simatic PDM.