22 9880023200-CU 36P NEUTRO 120312
CAUTION: NEVER CHECK FOR LEAKS WITH A FLAME.
WHEN LEAK CHECK IS COMPLETE, WIPE OFF ALL RESIDUE.
i) Remove shipping polystyrene from ALL rangetop burners. This is to hold
the burners in place on the burner base for shipping purposes only. This
should be done last
CHECKING PRESSURE OF HOUSE PIPING SYSTEM
1) The appliance and its individual shutoff valve must be disconnected from
the gas supply piping system during any pressure testing of that system at
test pressure in excess of ½ lbs./sq. in. (3.5 kPa or 13.8 in. water column).
2) The appliance must be isolated from the gas supply piping system by
closing its individual manual shutoff valve during any pressure testing of
the gas supply piping system at test pressure equal to or less than ½
lbs./sq. in. (3.5 kPa or 13.8 in. water column).
■
GAS CONVERSION
MOD: Oven Gas Range – Oven Dual Fuel Range
NOTE: All gas adjustment must be done by a qualified service
personnel only.
All Ranges are equipped with both Natural Gas and LP Gas injectors as well
as a convertible appliance pressure regulator. The unit model number plate
states which gas it was adjusted for at the factory. To convert the unit to
either Natural gas or LP gas will require switching burner injectors, the by-
pass screw (where necessary) and adjustment of the appliance pressure
regulator converter cap.
Inlet pressure to the appliance pressure regulator should be as follows for
both operation and checking of appliance pressure regulator setting:
INLET PRESSURE IN INCHES OF WATER COLUMN.
PRESSURE
Minimum Maximum
Natural gas
4
7
LP gas
11
14
GAS BURNER INJECTOR CONVERSION
To switch injectors, it is enough to unscrew fixed injector using a proper
7 Hex. key tool and replace it with new injector for new gas setting.
For proper injector size, follow the Technical Data chart (page 24) and fig. 10.