3-2
SMA America
SB3800U-12:SE2006
• If the inverter is installed outside, it should be mounted vertically or tilted back. (See
Figure 3-1).
Figure 3-1 Sunny Boy Mounting Positions
CAUTION: The SB3800U weighs 85 lb. (38 kg.). Ensure
that the mounting surface is strong enough to hold the
weight of the SB3800U. Do not mount the Sunny Boy on
plasterboard (sheet-rock) or thin wood panelling.
CAUTION: All electrical conduits and any communication
cables must be positioned and/or sealed so that no water
can enter the inverter enclosure through these conduits and
cables.
CAUTION: Do not install the SB3800U during periods of
precipitation or high humidity (>95%). Moisture trapped
within the enclosure may cause corrosion and damage to
the electronic components.
CAUTION: If you are installing the Sunny Boy in a cabinet,
closet, or other relatively small enclosed area, you must pro-
vide sufficient air circulation to dissipate the heat generated
by the inverter.
WARNING: To prevent electrical shock or other injury,
check for existing electrical or plumbing installations in the
walls before drilling mounting holes for the Sunny Boy.
CAUTION: Outdoor installations must use raintight or wet
location hubs that meet the requirements of the Standard for
Fittings for Cable and Conduit, UL514B.
Vertical
(Best option)
Tilted Back
(Acceptable)
Tilted Forward
(Unacceptable)
Summary of Contents for Sunny Boy 3800U
Page 1: ...5WPP Q 7 PUVCNNCVKQP WKFG...
Page 2: ......
Page 14: ...2 2 SMA America SB3800U 12 SE2006...
Page 22: ...3 8 SMA America SB3800U 12 SE2006...
Page 28: ...4 6 SMA America SB3800U 12 SE2006...
Page 70: ...Displays and Messages 7 22 SMA America SB3800U 12 SE2006...
Page 76: ...8 6 SMA America SB3800U 12 SE2006...
Page 80: ...9 4 SMA America SB3800U 12 SE2006...
Page 84: ...10 4 SMA America SB3800U 12 SE2006...
Page 85: ......
Page 86: ......