5-4
SMA America
SB3800U-12:SE2006
Percent voltage drop for 208 V AC and 240 V AC service
Figure 5-2 Energy Losses in Various Wire Sizes and Wire Lengths
The SB3800U is designed to automatically detect which grid voltage it is feeding if a
neutral is connected to the inverter. Depending upon the voltage and phase angle
between L1-N and L2-N, the inverter will determine if it is connected to a 208 V or 240
V grid. Table 5-1 lists the voltage and frequency limits for the AC connection.
Table 5-1 Voltage and Frequency Limits for the AC Connection
Voltage Range for 208 V nominal, line to line
183 V - 229 V
Voltage Range for 240 V nominal, line to line
211 V - 264 V
Frequency Range
59.3 Hz - 60.5 Hz
0,0%
One way distance (feet)
20
40
80
120
160
200
240
0,4%
0,8%
1,2%
1,6%
2,0%
Percent of 208 V AC and 240 V AC
60
100
0
140
180
220
8 AWG
6 AWG
10 AWG
12 AWG