9.3.2 Replacing optional string fuses
PV String Fuse Sizing
DC Disconnect Requirements
National Electrical Code
®
690.15-18 allows the use of fuse holders as a suitable means of
disconnecting PV arrays for servicing. Additional DC disconnects external to the inverter may be
required by the local authority having jurisdiction.
CAUTION
The string fuse size must not be greater than the maximum fuse size rating of the PV module
as provided on the PV module manufacturers data sheet. If no maximum fuse size is
indicated, please contact the PV module manufacturer!
Refer to section 14 ”Accessories” (page 108) for a specification of suitable fuses.
WARNING
Never remove a fuse while it is under load. Electrical arcing and damage to the fuse holder
will occur if a fuse is removed under load.