12 Technical Data
SMA Solar Technology AG
62
SB13_21TL-IA-en-65
Installation Manual
Protective Devices
Climatic Conditions in Accordance with IEC 60721-3-4, Installation Type C,
Class 4K4H
Climatic Conditions in Accordance with IEC 60721-3-4, Transport Type E,
Class 2K3
Degree of protection according to IEC 60529
IP65
Protection class according to IEC 62103
I
Grid configurations
TN-C system, TN-S system, TN-C-S system,
TT system, when V
N_PE
> 30 V, IT system,
Delta-IT system, Split Phase
Licences (as per 04/2013)
CE, VDE0126-1-1, G83/1-1, RD 661/2007,
PPC, AS 4777, EN 50438, C10/11, PPDS,
UTE C15-712-1, VDE-AR-N 4105, CEI 0-21,
RD1699*, NRS 097-2-1**, DIN EN 62109-1,
IEC 62109-2***
* To find out about restrictions in certain regions, contact the SMA Service Line.
** This standard stipulates that a special label be attached to the AC distribution to draw attention to the AC-side
disconnection of the inverter in the event of grid failure (for more details, see NRS 97-1-2, Sec. 4.2.7.1 and 4.2.7.2)
*** In order to meet the requirements of this standard, use of the fault indication relay must be activated in the inverter or there
must be a link to Sunny Portal with the fault alert via e-mail activated.
DC reverse-polarity protection
short-circuit diode
Input-side disconnection device*
* optional
Electronic Solar Switch
DC overvoltage protection
thermally monitored varistors
AC short-circuit protection
current control
Grid monitoring
SMA Grid Guard 2.1
Maximum permissible fuse protection
16 A
Earth fault monitoring
Insulation monitoring: R
iso
> 1 MΩ
All-pole sensitive residual-current monitoring unit
installed
Extended temperature range
− 25°C to +60°C
Extended humidity range
0% to 100%
Extended air pressure range
79.5 kPa to 106 kPa
Temperature range
− 25°C to +70°C