SMA Solar Technology AG
12 Technical Data
Installation Manual
SB13_21TL-IA-en-65
61
Efficiency
General Data
Operating range at AC mains
frequency 50 Hz
44 Hz to 55 Hz
44 Hz to 55 Hz
44 Hz to 55 Hz
Operating range at AC mains
frequency 60 Hz
54 Hz to 65 Hz
54 Hz to 65 Hz
54 Hz to 65 Hz
Power factor at rated power
1
1
1
Feed-in phases
1
1
1
Connection phases
1
1
1
Overvoltage category according to
IEC 60664-1
III
III
III
SB 1300TL-10
SB 1600TL-10
SB 2100TL
Maximum efficiency, η
max
96.0%
96.0%
96.0%
European weighted efficiency, η
EU
94.3%
95.0%
95.2%
Width x height x depth
440 mm x 299 mm x 214 mm
Width x height x depth, with ESS
440 mm x 339 mm x 214 mm
Weight
16 kg
Length x width x height of packaging
532 mm x 392 mm x 318 mm
Weight with packaging
21.2 kg
Climatic category according to IEC 60721-3-4
4K4H
Environment category
outdoors
Degree of pollution outside the enclosure
3
Degree of pollution inside the enclosure
2
Operating temperature range
− 25°C to +60°C
Maximum permissible value for relative humidity,
non-condensing
100%
Maximum operating altitude above MSL
2,000 m
Noise emission (typical)
≤ 33 dB(A)
Power loss in night mode
0.1 W
Topology
transformerless
Cooling concept
convection
SB 1300TL-10
SB 1600TL-10
SB 2100TL