SMA Solar Technology AG
Parameter lists
Technical Description
SI5048-TEN093630
153
09
GdRvPwr
Permissible grid
reverse power
(active power)
100 W
10
GdRvTm
Permissible time for
grid reverse power
100 W
15
GdAlSns
AI sensitivity
Low
low
Normal
Medium
Medium
Normal
Normal
High
high
37
GdVtgIncProEna Voltage rise
protection
Disable
Enable
Enable
Enable
Disable
38
GdVtgIncPro
Boundary for voltage
increase protection
230 V / 50 Hz 253 V
220 V / 60 Hz 242 V
40
Country
Installation country
The installation land is
set based on the
corresponding
applicable norm.
The defaut value is set
according to your
order.
GER_VDE01
26_1_1
Germany
AS4777
USA
Other
others
41
FedInMod
Feeding into the grid
The value defines that
upon which the feed-
in is dependent.
Off
off
Off
Time
Time
Signal
digital signal
Com
Communicatio
n
SignalCom
42
FeInSocStr
SOC limit for grid
feeding start time
70 %
43
FedInSocStp
SOC limit for grid
feeding stop time
60 %
44
FedInTmStr
Start time for time-
dependent grid
feeding in hh:mm:ss
45
FedInTmStp
Stop time for time-
dependent grid
feeding in hh:mm:ss
Number Name
Description
displayed
value
Description
Default
value