SMA Solar Technology AG
Parameter lists
Technical Description
SI5048-TEN093630
151
225# Battery Current Sensor
226# BMS Mode Basic/Off
Number Name
Description
Value
Description
Default
value
01
BatCurSnsTyp
Battery current sensor
type
None
No sensor is
connected.
None
60 mV
Battery Current
Sensor 60 mV
50 mV
Battery Current
Sensor 50 mV
02
BatCurGain60
External battery current
sensor type
(60 mV type)
A/60
mV
100 A
03
BatCurGain50
External battery current
sensor type
(50 mV type)
A/50
mV
100 A
04
BatCurAutoCal
Automatic calibration of
the external battery
current sensor
Start
Number Name
Description
displayed
value
Default
value
01
BatChrgVtgMan
Manual battery charge nominal
voltage with deactivated BMS
41 V ... 63 V
54 V
02
BatDiChgVtg
Minimum discharging voltage
42 V ... 46 V
44 V
03
BatDiChgVtgStr
Start voltage after battery
undervoltage detection
46 V
04
BatRes
Internal resistance of battery
0 mOhm ...
200 mOhm
0 mOhm