Parameter lists
SMA Solar Technology AG
150
SI5048-TEN093630
Technical Description
223# Battery Protection Mode
224# Battery Silent Mode
Number Name
Description
displayed
value
Default value
01
BatPro1TmStr
Starting time of the battery-
preservation mode (level 1)
22:00:00
hh:mm:ss
02
BatPro1TmStp
End time of battery-preservation
mode (level 1)
06:00:00
hh:mm:ss
03
BatPro2TmStr
Starting time of the battery-
preservation mode (level 2)
17:00:00
hh:mm:ss
04
BatPro2TmStp
End time of battery-preservation
mode (level 2)
09:00:00
hh:mm:ss
05
BatPro1Soc
Battery charge state for battery-
preservation mode level 1
0 % ... 70 %
20 %
06
BatPro2Soc
Battery charge state for battery-
preservation mode level 2
0 % ... 70 %
15 %
07
BatPro3Soc
Battery charge state for battery-
preservation mode level 3
0 % ... 70 %
10 %
Number Name
Description
Value
Description
Default
value
01
SilentEna
Silent mode on the grid Disable Enable
Disable
Enable
Disable
02
SilentTmFlo
Maximal time for float
charge until transfer into
silent
1 h ...
48 h
3 h
03
SilentTmMax
Maximal time for silent
until transfer into float
charge
1 h ...
168 h
12 h