SMA Solar Technology AG
Parameter lists
Technical Description
SI5048-TEN093630
157
235# Generator Start
Number Name
Description
Value
Description
Default
value
01
GnAutoEna
Generator autostart
Off
Disable
On
On
Enable
02
GnAutoStr
Number of autostarts
3
03
GnSocTm1Str
SOC limit for switching
on generator for time 1
40 %
04
GnSocTm1Stp
SOC limit for switching
off generator for time 1
80 %
05
GnSocTm2Str
SOC limit for switching
on generator for time 2
40 %
06
GnSocTm2Stp
SOC limit for switching
off generator for time 2
80 %
07
GnTm1Str
Time 1 for generator
request in hh:mm:ss
Begin: Time 1,
End: Time 2
08
GnTm2Str
Time 2 for generator
request in hh:mm:ss
Begin: Time 2,
End: Time 1
09
GnPwrEna
Generator request
based on power
Off
Disable
Off
On
Enable
10
GnPwrStr
Generator request
switch-on power limit
4 kW
11
GnPwrStp
Generator request
switch-off power limit
2 kW
12
GnPwrAvgTm
Average time for
power-related
generator start
60 sec
13
GnTmOpEna
Time-controlled
generator operation
Disable Enable
Disable
Enable
Disable
14
GnTmOpStrDt
Starting date for time-
controlled generator
operation
2006.01.01
yyyy.mm.dd
15
GnTmOpStrTm
Starting time for time-
controlled generator
operation in hh:mm:ss
Summary of Contents for SI 5048