Quick Setup/Installation Guide for Lubrication Monitor Controller LMC 301
951-150-029-EN
21
6.3 Menu navigation for system coniguration -
Progressive pump settings with Supervisor password
Supervisor password
factory setting:
2020
Fig. 22
Login settings
User settings
Device settings
Pump 1 Timings
System configuration
Information
Main Menu
Login settings
Enter Password
Set PW local admin
Set PW Supervisor
Enter Password
Please enter Password
to continue
0000
Password correct
You are logged in
as Supervisor
Login settings
System configuration
Amount of pumps
Pump 1 settings
Set Params to Default
Restore Fact. Set.
Amount of pumps
Pump 1 settings
Pump settings
Zone 1 Settings
Zone 2 Settings
Zone 3 Settings
Pump Settings
System Type
Lube control
Filling/Low Level
Motor Protection
Temperature Control
System Type
System Type
[
<< Single Line >>
<< Progressive >>
<< Dual Line >>
]
Zone
[ 3 Zone ]
TZone vent valve type
[ <<2/2 Way Valve NO >> << 2/2 Way Valve NC >> << 3/2 Way Valve>> ]
Lube Control
Pump Output
Output Type
[ <<normally closed>> <<normally open>> << disabled>>
Output No.
[ 1,01 ] O
Remote Manual Lube
Input Type
[ <<
disabled >> << normally open>>
<< normally closed >>]
Input No.
[1,05] DI
Filling/Low Level
Monitoring
Alarm
Inputs
Timings
Monitoring
Filling Monitoring type
[ << Low Level Detection>> << Auto Filling>> <<disabled>>
Lube Limited By
[ << LL Lube Cycles>> << LL Pump time>> << disabled >>
Alarm
Output Type
[ << normally closed>>
<< normally open>> << disabled>>
Output No
[ 1,02 ] O
Inputs
Input LL Type
<< disabled>> << transducer 1-6V >> << transducer4-20 mA >> transducer 0-20mA >>
<<transducer 2-10V >> <<transducer 0-10V>> << normally open>> << normally closed >> ]
Input No LL
[ 1,03 ] DI
Timings
Filling Timeout
[ 00: 00: 00 ]
Detection LL Time
[ 10]
Motor Protection
Motor Protection Type
[ << normally open>> << normally closed>> <<disabled>>
Input No.
[ 1, 04 ] DI
Amount of pumps
[
<< 1 pump >> << 2 pump>> << 3 pump >>]
Login settings
Filling/Low Level
Motor Protection/
Temperature Control
Pump Output
Sensor at Pump Set.
Remote Manual Lube
Lube Control
Sensor at Pump Set.
Sensor Type
[
<< disabled>> << transducer 1-6V >>
<< transducer 4-20 mA >> transducer 0-20mA >>
<<transducer 2-10V >> <<transducer 0-10V>>
<< Öffner >> << Schließer >> ]
Input No.
[1,04] DI
Minimal Valve
[ 0] bar
Maximal Valve
[ 0] bar
Maximal System Valve
[ 0] bar
Additional monitoring
Temperature Control
Internal Sensor
Externalr Sensor
Temperature Limits
Internal Sensor
InternalSensor
[ << disabledt>><< enabled>>]
IO Board
[ 1 ]
External Sensor
Sensortyp
[
<< disabled>> << transducer 1-6V >> << transducer 4-20 mA >>
<<transducer 0-20mA >><<transducer 2-10V >> <<transducer 0-10V>>
<<normally closed>> <<normally open>>]
Input
[ 1,02 ] AI
Minimal Valve
[ 0000 ] PSI
Maximal Valve
[ 0000 ] PSI
Note!
Additional buttons for transducer setting
Temperature Limits
Over temperature
[ 180,0 ] F
Under temperature
[ 14,0 ] F
Set Params to Default
Set Params to Default?
Continue?
Restore Fact. Set.
Restore Fact. Set?
Continue?