Technical Documentation 

 

  

 

The Fire control panel  

SCP-03  

 

 

 

 

 

 

Rev.02

 

 
 

Summary of Contents for SCP-03

Page 1: ...SKALMEX Sp z o o ul Boczkowska 7 Skalmierzyce 63 460 Nowe Skalmierzyce tel 0 62 762 10 39 Strona 1 Technical Documentation The Fire control panel SCP 03 Rev 02...

Page 2: ...ilure to follow the instructions contained in this manual may be dangerous or cause damage to the control unit SKALMEX Sp z o o is not liable for damages resulting from operating contrary to the follo...

Page 3: ...nel technical data 4 Configuration and data reading options 4 1 Level 1 4 2 Level 2 4 3 Level 3 5 Description of control panel operating states 5 1 Smoke alarm status 5 2 Main alarm status 5 3 Supervi...

Page 4: ...points manual smoke exhaust buttons and external alarm signals control of fire fighting devices smoke exhaust damper gate or fire lock fire information transfer to external security systems alarm 1 3...

Page 5: ...t least once a year All repairs must be carried out by the manufacturer SKALMEX Sp z o o is not responsible for the operation of equipment maintained and repaired by unauthorized companies 1 4 Deliver...

Page 6: ...ith a frequency of at least once a year 3 The warranty period is 24 months provided that the control panel has been installed by SKALMEX Sp z o o or an authorized company for assembly 12 months when t...

Page 7: ...battery voltage and the presence of the mains supply are also checked in the event of a power outage there is an automatic uninterrupted power supply switching to the backup battery mode The battery c...

Page 8: ...tic closure of the damper after a set time ventilation option Automatic damper closing after mains power failure option Limitation of the damper extension time adjustable by potentiometer option Autom...

Page 9: ...ature range 20 C 50 C Supply voltages and output currents 50 Hz 230 V network 10 15 Reserve battery 2 x 13 8 V 2x2 3Ah Voltage supply of external devices stabilized 24 V 10 10 Voltage supply of extern...

Page 10: ...tion line 1 0 25 0 6W End resistor of the smoke damper actuator 4k7 1 0 25 0 6W Optional series 1k 1 0 25 0 6W detection line resistor some detection devices e g buttons have this resistor already bui...

Page 11: ...lock Only authorized persons access Access level 3 includes the programming connector of the control panel access is limited by blocking the ability to read data Only persons authorized by SKALMEX Sp...

Page 12: ...3 switches are used to set the ventilation time SW1 1 SW1 2 SW1 3 Minutes 0 0 0 0 1 0 0 6 0 1 0 15 1 1 0 60 0 0 1 90 1 0 1 180 0 1 1 240 1 1 1 360 The time can be shortened by 2 minutes if the dip swi...

Page 13: ...OFF position applies to the SAP signal with NO output The drawing is on page 26 Ad b P1 Potentiometer for adjusting the time of incomplete opening of the smoke exhaust damper For a correct re counting...

Page 14: ...fire sensor line 1 1 1 0 Short circuit in the RESET line of the manual smoke exhaust button 0 0 0 1 A break in the RESET line of the manual smoke exhaust button 1 0 0 1 Short circuit of the manual sm...

Page 15: ...connecting the control unit to the power supply it turns off or on the signaling of brake errors Switching off will be signaled by blinking of all four error LEDs D1 D4 and switching on by blinking o...

Page 16: ...aust alarm status the control panel does not respond to manual control of the smoke exhaust flap and other signals that may disturb correct operation in the alarm state the red diode with the signatur...

Page 17: ...control of the smoke exhaust damper and the fire gate as well as other signals that may interfere with proper operation in the alarm state the red LED with the signature ALARM lights continuously on...

Page 18: ...control panel cover or if the control panel has switched to battery power the LED with the BATTERY signature will light up 5 4 Testing status Entering the testing state is possible by prolonged press...

Page 19: ...f the lines checked the diode with the signature TROUBLE on the control panel cover and the diodes D1 D2 D3 D4 on the panel cover display the error number This condition does not affect the control pa...

Page 20: ...lmierzyce 63 460 Nowe Skalmierzyce tel 0 62 762 10 39 Strona 20 6 Installation of the control panel The device is installed using 4 wall plugs of a size not less than 6 mm The location of the mounting...

Page 21: ...ables are fit into the switchboard from below through cable inlets It is recommended to insert the detection lines as far as possible from each other from the 230VAC cable supplying the control panel...

Page 22: ...he active state of the input is during a short to GND do not connect these inputs to any other voltages To the output of information LEDs connect the LEDs with anode to the appropriate output network...

Page 23: ...OTOR CONTROL connector and connect to the connector a device for controlling the speed of opening the fire gate which may interrupt the power supply circuit of the relays controlling the up down gate...

Page 24: ...e smoke exhaust damper can be done by means of ventilation buttons it is possible to open and close it The SW2 1 configuration switch can be selected with the option to support ventilation buttons i e...

Page 25: ...is set by the P1 potentiometer the range of available times is from 0 50s After incomplete opening of the smoke vent you should wait a minimum of 8 minutes before re opening again Not waiting a certa...

Page 26: ...the brakes PE protective conductor 1 N neutral cable of 230v network 2 L UP phase conductor when voltage occurs on it the motor will rotate in the up direction 3 L DOWN phase conductor when voltage o...

Page 27: ...24VDC signaling device output e g bulb or other which turns on during an alarm Motor Control input optional input for an overspeed prevention device To use them solder the tin jumper next to the conn...

Page 28: ...P1 in the figure the other without P2 in the figure in the absence of a built in resistor such resistor R3 in the figure should be connected in series with the button as shown At the end of the line c...

Page 29: ...762 10 39 Strona 29 SMOKE VENT MOTOR 24VDC smoke damper motor SMOKE VENT buttons for manually opening S5 and closing S6 smoke flaps GATE buttons for manually opening S3 and closing S4 the gate LED si...

Page 30: ...s signal with a COM signal NC Normal Connected signal shorted to COM signal with the relay turned off after switching on the signals are opened COM common signal List of relay outputs ENDSTOP UP motor...

Page 31: ...the control panel and devices cooperating with it The maintenance technician should have full knowledge of the object in which the system is installed If ionizing smoke detectors are used in the inst...

Page 32: ...one if necessary checking the operation of external signaling performing alarm simulation after prior agreement and informing all persons within the zone in which the alarm simulation is being carried...

Page 33: ...re Storage The control panel should be stored in rooms at a temperature of 0 40 C and a relative humidity of not more than 70 In case of longer storage the control panel should be connected to the pow...