Strona
12
Level 2
At this level are available:
a) Configuration switches
SW1, SW2, SW3
b)
P1
control potentiometers
c) Diodes for reading errors
D1, D2, D3, D4
d)
B1
button
e)
D5
test diode
f)
D6
hardware watchdog LED
Ad. a
The first 3 switches are used to set the ventilation time
SW1.1
SW1.2
SW1.3
Minutes
0
0
0
0
1
0
0
6
0
1
0
15
1
1
0
60
0
0
1
90
1
0
1
180
0
1
1
240
1
1
1
360
The time can be shortened by 2 minutes if the dip switch is off
SW2.1
SW1.4
-Inclusion of incomplete opening of the smoke vent
SW2.1
-Supporting the ventilation buttons (once briefly pressing the
ventilation button causes the smoke exhaust damper to move to the
end position).
SW2.2
-Blocking the option of external alarm reset caused by the
manual smoke exhaust button.