SJE
®
5
VFDC-3000 Controller User Manual
CONTROLLER SETPOINTS LIST
STATION NAME
START UP DATE
CONTROLLER REVISION
SETTING
MIN MAX UNITS DEFAULT USER SETTING
BASIC SETTINGS
Setpoint Pressure
0.0
*1
PSI
60.0
Sleep Frequency
0.0
*2
Hz
35.0
Sleep Delay Time
0.0
999.9
Seconds
10.0
Minimum Frequency
0.0
*2
Hz
30.0
Maximum Frequency
0.0
65.0
Hz
60.0
Lead Pump Start Differential Pressure
*1
0.0
PSI
-5.0
Lag Pump Start Differential Pressure
*1
0.0
PSI
-7.0
Lag Pump Stop Differential Pressure
0.0
*1
PSI
7.0
Alternation
Alternate/P1 Lead/P2 Lead/P3 Lead
Alternate
Alternation Time
1.0
999.9
Hours
24.0
Low Pressure Alarm
0.0
*1
PSI
15.0
Low Pressure Alarm Delay Time
0.0
999.9
Seconds
20.0
Low Pressure Alarm Reset Delay Time
0.0
999.9
Minutes
0.0
High Pressure Alarm
0.0
*1
PSI
75.0
Low Water Delay Time
0.0
999.9
Seconds
10.0
PUMP SETTINGS
Acceleration
0.0
3600.0
Seconds
3.0
Deceleration
0.0
3600.0
Seconds
3.0
Thrust Bearing Frequency
0.0
*2
Hz
0.0
Thrust Bearing Acceleration
0.0
3600.0
Seconds
2.0
Pump 1 Overload Amps
0.0
999.9
Amps
*3
Pump 1 Motor Voltage
0.0
999.9
Volts
*3
Pump 2 Overload Amps
0.0
999.9
Amps
*3
Pump 2 Motor Voltage
0.0
999.9
Volts
*3
Pump 3 Overload Amps
0.0
999.9
Amps
*3
Pump 3 Motor Voltage
0.0
999.9
Volts
*3
ADVANCED SETTINGS
Sensor Range
1.0
999.9
PSI
200.0
Sensor Offset
-999.9
999.9
PSI
0.0
PID Proportional Term
0
999
70
PID Integral Term
0
999
35
PID Derivative Term
0
999
1
Setpoint Pressure 2
0.0
*1
PSI
40.0
Pipe Fill Frequency
0.0
*2
Hz
30.0
Pipe Fill Time
0.0
999.9
Seconds
0.0
Low Suction Delay Time
0.0
999.9
Seconds
10.0
Low Suction Reset
AUTO/MANUAL
AUTO
Low Suction Reset Delay Time
0.0
999.9
Seconds
10.0
Idle Prevention Exercise Schedule
0.0
999.9
Days
0.0
Pump 1 Jockey
ENABLED/DISABLED
DISABLED
Jockey Pump Stop Delay Time
0
999
Seconds
0
Number of Pumps
1
3
3
Maximum Pumps On
1
3
3
Relay 1 Function
*4
GEN. ALARM
Relay 2 Function
*4
HIGH PRESS
Relay 3 Function
*4
LOW PRESS
Relay 4 Function
*4
P1 RUN
Relay 5 Function
*4
P2 RUN
Relay 6 Function
*4
P3 RUN
VFD 1 Hand Speed
0.0
*2
Hz
45.0
VFD 2 Hand Speed
0.0
*2
Hz
45.0
VFD 3 Hand Speed
0.0
*2
Hz
45.0
Language
ENGLISH/ESPAÑOL
ENGLISH
*1 - Value based on “Sensor Range” setting
*2 - Value based on “Maximum Frequency” setting
*3 - Value based on output rating of variable frequency drive
*4 - Settings include: P1 Run, P2 Run, P3 Run, P1 Fault, P2 Fault, P3 Fault, High Press, Low Press, Low Suction, Low Water, General Alarm