10 Type IFS Operation Manual
HAND/OFF/AUTO OPERATION
PRESS - ENTER
The HAND, OFF, or AUTO operating mode can be
changed for each pump independently.
• An AUTO or OFF setting will always return the
user to the main screen upon selecting.
• A HAND setting will return to the main screen
upon selecting if the tank level is above the
lowest float or the level sensor’s lowest
setpoint. Once the tank level drops to the
lowest float or the level sensor’s lowest
setpoint, the controller will automatically be
changed to AUTO mode.
• If the tank level is lower than the lowest
float or the level sensor’s lowest setpoint,
then the user must press and hold the enter
button to enable HAND mode. Upon releasing
the enter button, in this case, the controller
will automatically be changed to AUTO mode
and will return to the main screen.