SJE Rhombus
®
16 Type IFS Operation Manual
I/O TABLES
TB1 - SUPPLY POWER, LEVEL SENSING, PUMP
AND AUXILIARY ALARM CONTACTS
TERMINAL
DESCRIPTION
1
90-265 VAC SUPPLY
2
90-265 VAC SUPPLY
3
DIGITAL INPUT COMMON
4
DIGITAL INPUT 1
5
DIGITAL INPUT COMMON/C-LEVEL
NO-CONNECTION
6
DIGITAL INPUT 2/C-LEVEL (+) SUPPLY
7
DIGITAL INPUT COMMON/C-LEVEL (-) SUPPLY
8
DIGITAL INPUT 3/C-LEVEL SIGNAL INPUT
9
DIGITAL INPUT COMMON
10
DIGITAL INPUT 4
P1:T1
PUMP 1 (T1)
P1:T2
PUMP 1 (T2)
P2:T1
PUMP 2 (T1)
P2:T2
PUMP 2 (T2)
AUX:1
AUXILIARY ALARM CONTACT (N.O.)
AUX:2
AUXILIARY ALARM CONTACT (N.O.)
TB3- PUMP SUPPLY POWER
TERMINAL
DESCRIPTION
P1:L1
PUMP 1 (L1)
P1:L2
PUMP 1 (L2/N)
P2:L1
PUMP 2 (L1)
P2:L2
PUMP 2 (L2/N)
TB2- HORN, BEACON, TEST/SILENCE SWITCH,
AUX 24VDC SUPPLY
TERMINAL
DESCRIPTION
1
TEST/SILENCE/RESET SWITCH (1)
2
TEST/SILENCE/RESET SWITCH (2)
3
ALARM LIGHT (0V)
4
ALARM LIGHT (24V)
5
ALARM HORN (0V)
6
ALARM HORN (24V)
7
AUX 24VDC SUPPLY (-)
8
AUX 24VDC SUPPLY (+)
All Digital Input functions are activated upon a
contact closure to the Digital Input Common
terminal.
Note:
Terminals TB1-3, TB1-5, TB1-7, TB1-9 commons
are internally connected.
J5 - ALARM 2, OVERLOAD 1, OVERLOAD 2
TERMINAL
DESCRIPTION
1
ALARM 2 INPUT
2
OVERLOAD 1 INPUT
3
OVERLOAD 2 INPUT
4
DIGITAL INPUT COMMON
5
DIGITAL INPUT COMMON
6
DIGITAL INPUT COMMON
*J5
6
4
3
1