     14                                                  Type IFS Operation Manual

TROUBLESHOOTING INFORMATION SCREENS

Current Panel Configuration

Duplex
Timed Dose
C-Level

 Sensor

40” Sensor

This section displays the current configuration of the controller. *The example shows a controller 
configured as a Duplex, Timed Dose using a 40” C-Level

 sensor for level sensing.

C-Level

 Status

Simulator
Frequency 

  2315 

Hz

Tank Level   

 

26.3 in

The simulator is used to verify the functionality of the controller by simulating the tank level.

This section displays the frequency of the C-Level

 sensor as measured by the controller, as well 

as the calculated tank level. The normal operating range of the C-Level

 sensor is between 1000Hz 

and 3000Hz. If the C-Level

 sensor frequency is operating significantly outside of the normal range, 

a “Sensor Fail” alarm will occur.

Float Status

Redundant High Level 

Down

Redundant Low Level 

Up

This screen displays the status of each float switch connected to the controller. *The example shows a 
controller configured as C-Level™ sensor control.

Pump Status

Pump 1 Called 

 

Off

Pump 1 Amps  

 

0.0 A

Pump 2 Called 

 

Off

Pump 2 Amps 

 

0.0 A

This screen displays the status of each pump connected to the controller. *The example shows a 
controller configured as Duplex.

Alert Status

Horn 

   Off

Beacon   Off
Alarm 

Aux 

  Off

This screen displays the status of the controller alarm.

Summary of Contents for IFS

Page 1: ... L1 L2 P1 L1 L2 P2 AUX 24VDC ALARM HORN STATUS IN IN2 IN3 IN4 EXP J5 L1 L2 P2 Installer Friendly Series SJE RHOMBUS Type IFS Operation Manual Technical support 1 800 746 6287 techsupport sjeinc com www sjerhombus com Technical Support Hours Monday Friday 7 A M to 6 P M Central Time ...

Page 2: ...reen Programming 3 User Interface 3 Main Menu 4 HAND OFF AUTO Operation 10 Clearing Counts and ETMs 11 Alarms 12 Troubleshooting Information Screens 13 I O Tables 17 Mounting Dimensions 18 Controller Dimensions 18 Schematic Example 19 SJE Rhombus Type IFS Operation Manual ...

Page 3: ...tall in hazardous locations as defined by National Electrical Code ANSI NFPA 70 Do not connect power to this equipment if it has been damaged or has any missing parts Do not install in areas with excessive or conductive dust corrosive or flammable gas moisture or rain excessive heat regular impact shocks or excessive vibration SJE Rhombus 1 Type IFS Operation Manual Warning Users must read this ma...

Page 4: ...ump run indication 1 2 Pump power relays 240 Vac 20A max SYSTEM Alarm counts Pump cycle counts Pump run time ELECTRICAL SPECIFICATIONS Universal 85 265 Vac 50 60Hz Control Alarm power input 0 250 Vac 50 60Hz 20A max Pump Power input 5kA short circuit current rating 24 Vdc class 2 control power Auxiliary Power 24 Vdc 100mA max DEDICATED I Os 4 Float switch inputs C Level sensor with 2 backup floats...

Page 5: ...E Rhombus 3 Type IFS Operation Manual Pump HAND OFF AUTO Status Selection Pump Hour Meter selectable Settings Menu Graphical Setpoint Bars C Level Level Bar Graph or Float Status Tank Level C Level Color Liquid Crystal Display LCD Menu Navigation And ENTER Dial Graphical Timer Count Down indicated on lead pump Pump Cycle Counts selectable Pump Amps selectable not shown ...

Page 6: ...d dose mode only Configures timers for timed dose operation Level Settings Configures level setpoints Alternation duplex only Configures alternation mode for duplex panels Advanced Configures advanced functions and accesses troubleshooting tools Back Exits the Main Menu SJE Rhombus 4 Type IFS Operation Manual ...

Page 7: ...0 Pump 2 Seal Sensor Fail 0 0 Back visible only for duplex controllers Timer Settings Timed Dose Mode Only Pump 1 On Time Off Time Override On Time Override Off Time Pump 2 On Time Off Time Override On Time Override Off Time Back visible only for independent timers mode Level Settings C Level Mode Only Timed Dose Mode Simplex Demand Dose Mode Duplex Demand Dose Mode save and exit X exit without sa...

Page 8: ...s On General Back Level Sensing Float Switches C Level Sensor Back C Level Range when C Level Sensor is selected 40 Sensor Timed Demand Dose Timed Dose Demand Dose Back Timer Type when Timed Dose is selected duplex panels only Single Timer Independent Timers Back Expansion Port Seal Fail Thermal when Expansion Port is enabled Enable Enable Disable Disable Back Back 100 Sensor Back Allows for two i...

Page 9: ...ller with C Level only Seal Fail Alarm when Seal Fail Thermal Module enabled Thermal Alarm when Seal Fail Thermal Module enabled Overload Alarm when Overload Cutout enabled Back Beacon Flash No Flash No Flash Flash All Flash Alarm 2 Only Back Horn Flash Flash All Flash Alarm 2 Only Back Manual Reset Redundant High Water Lag Seal Fail Alarm Thermal Alarm Overload Alarm Enable Enable Enable Disable ...

Page 10: ...us Horn Off Beacon Off Alarm Aux Off Input Status Test Silence Off Alarm 2 Off Overload 1 Off Overload 2 Off Fault Status Pump 1 Inactive Thermal 1 Inactive Seal 1 Inactive Pump 2 Inactive Thermal 2 Inactive Seal 2 Inactive Controller Status DC Bus 1 22 50 V DC Bus 2 11 80 V DC Bus 3 3 29 V Back Visible only for C Visible only for duplex configuration Level mode Float Status for duplex demand dose...

Page 11: ...play V 0 00 Controller V 0 00 Settings Language Color Theme Password Setup Back Language English Espanol Francais Back Color Theme Dark Light Back Password Setup 00 00 Enable save and exit X exit without saving Float Simulator C Level Sensor Simulator Simulator ...

Page 12: ...ank level is above the lowest float or the level sensor s lowest setpoint Once the tank level drops to the lowest float or the level sensor s lowest setpoint the controller will automatically be changed to AUTO mode If the tank level is lower than the lowest float or the level sensor s lowest setpoint then the user must press and hold the enter button to enable HAND mode Upon releasing the enter b...

Page 13: ...o be cleared To clear an individual count or ETM Navigate to the Counts and ETMs screen and to the data to be cleared Press and hold the enter button Navigate to Yes when asked to reset the value Navigate to Confirm to clear the count or ETM or to Cancel to exit without clearing the count or ETM Cancel Confirm Are You Sure Pump 1 ETM ...

Page 14: ... Fail The seal fail module has sensed a seal leak condition in Pump 1 based on the seal fail setting Service Pump 1 seal P1 Thermal Cutout The controller has sensed a change in the status of the Pump 1 thermal input on the Seal Fail Thermal Cutout expansion module Ensure Pump 1 motor thermal cutout is functioning correctly Ensure Pump 1 motor is functioning correctly P1 Fault The controller has op...

Page 15: ...ile the redundant off and higher level float switches have closed Ensure the float switches have been installed in the proper order Ensure the float switches do not contact the sides of the tank or objects in the tank Float Config Error The controller has sensed a C Level sensor signal connected to the field wiring terminals while configured as float switch controlled Ensure the controller is conf...

Page 16: ...troller as well as the calculated tank level The normal operating range of the C Level sensor is between 1000Hz and 3000Hz If the C Level sensor frequency is operating significantly outside of the normal range a Sensor Fail alarm will occur Float Status Redundant High Level Down Redundant Low Level Up This screen displays the status of each float switch connected to the controller The example show...

Page 17: ...troller Fault Status Pump 1 Inactive Thermal 1 Inactive Seal 1 Inactive Pump 2 Inactive Thermal 2 Inactive Seal 2 Inactive This section displays the fault status of each pump connected to the controller The example shows a controller configured as Duplex with a thermal seal fail module Controller Status DC Bus 1 22 41 V DC Bus 2 11 79 V DC Bus 3 3 29 V This section displays the status of the volta...

Page 18: ... ALARM CONTACT N O TB3 PUMP SUPPLY POWER TERMINAL DESCRIPTION P1 L1 PUMP 1 L1 P1 L2 PUMP 1 L2 N P2 L1 PUMP 2 L1 P2 L2 PUMP 2 L2 N TB2 HORN BEACON TEST SILENCE SWITCH AUX 24VDC SUPPLY TERMINAL DESCRIPTION 1 TEST SILENCE RESET SWITCH 1 2 TEST SILENCE RESET SWITCH 2 3 ALARM LIGHT 0V 4 ALARM LIGHT 24V 5 ALARM HORN 0V 6 ALARM HORN 24V 7 AUX 24VDC SUPPLY 8 AUX 24VDC SUPPLY All Digital Input functions ar...

Page 19: ...SJE Rhombus 17 Type IFS Operation Manual MOUNTING DIMENSIONS DISPLAY CONTROLLER DIMENSIONS ...

Page 20: ...SJE Rhombus 18 Type IFS Operation Manual SCHEMATIC EXAMPLE ...

Page 21: ...____________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ ___________________________________________________________...

Page 22: ... 21 2021 SJE Inc All Rights Reserved SJE RHOMBUS is a trademark of SJE Inc Technical Support 1 800 746 6287 techsupport sjeinc com www sjerhombus com Technical Support Hours Monday Friday 7 A M to 6 P M Central Time ...

Reviews: