SJE Rhombus
®
13 Type IFS Operation Manual
ALARMS - Continued
ALARM TEXT
DEFINITION
FIX
Stop Float Fail
The controller has sensed that the
stop float has failed to close while
higher level float switches have closed
• Ensure the float switches have been
installed in the proper order.
• Ensure the float switches do not
contact the sides of the tank, or
objects in the tank.
Lead Float Fail
The controller has sensed that the lead
float has failed to close while the stop
and higher level float switches have
closed.
• Ensure the float switches have been
installed in the proper order.
• Ensure the float switches do not
contact the sides of the tank, or
objects in the tank.
Off Float Fail
The controller has sensed that the
redundant off float has failed to close
while higher level float switches have
closed.
• Ensure the float switches have been
installed in the proper order.
• Ensure the float switches do not
contact the sides of the tank, or
objects in the tank.
Enable Float Fail
The controller has sensed that the
timer enable float has failed to close
while the redundant off and higher level
float switches have closed.
• Ensure the float switches have been
installed in the proper order.
• Ensure the float switches do not
contact the sides of the tank, or
objects in the tank.
Float Config Error
The controller has sensed a C-Level
™
sensor signal connected to the field
wiring terminals, while configured as
float switch controlled.
• Ensure the controller is configured for
C-Level
™
sensor.
C-Level
™
Error
The controller has sensed a signal
outside the normal operating range of
the C-Level
™
sensor.
• Ensure the controller is configured for
float switch control if a C-Level
™
sensor is not used.
• Ensure the C-Level
™
sensor is properly
connected to the controller.
• Ensure the C-Level
™
sensor cable has
not been damaged.
Alarm 2
A contact closure has been sensed by
the Alarm 2 input circuit.
• Check the system monitored by the
Alarm 2 input.
Alarm 3
A contact closure has been sensed by
the fourth digital input circuit when
in Simplex Demand mode or Duplex
Demand 3-Float mode.
• Check the system monitored by the
fourth digital input.
Press Test/Silence to Reset Alarm
The controller is configured for manual
alarm reset and the formerly active
alarm is now inactive.
• Press the Test/Silence button to reset
the alarm status.