INSTALLATION, OPERATING, & MAINTENANCE
SOLID STATE CONTROL HEATER
FOR OPERATION WITH PROPANE VAPOR, PROPANE LIQUID, AND NATURAL GAS
DANGER: THESE UNITS OPERATE WITH FLAMMABLE AND EXPLOSIVE GASES,
IMPROPER INSTALLATION, OPERATION, OR MAINTENANCE CAN CREATE
POTENTIAL DANGER. READ ALL INSTRUCTIONS CAREFULLY, AND OBEY ALL
CAUTIONS AND WARNINGS. FAILURE TO DO SO COULD RESULT IN SERIOUS
BODILY INJURY OR PROPERTY DAMAGE.
SHIPPING, RECEIVING AND INSPECTION
Review heater model number, confirming this is the model you ordered. Contact your dealer immediately
if otherwise. All cardboard cartons are shipped attached to heater, with power cord installed. Inspect
heater for damage, noting any found on freight bill.
PREPARING SITE FOR INSTALLATION
WARNING! Be sure to review pervious pages on model selection and warnings. Installation should be
performed only by a qualified dealer, who is experienced and familiar with grain drying equipment, and
with local codes, laws, and ordinances regulation gas and electrical installations. Improper installation
could result in serious bodily injury or property damage.
Before installing heater and controls- your locale gas company needs to review your site and read the
following information regarding your needs for a correct, safe installation, and operating future.
Heater Using Propane Vapor
A 1,000 gallon storage tank should provide adequate vaporization to ignite the heater within its capacities.
The heater should not be used if the tank is less than 20% full. The storage tank should be equipped with
a propane regulator with an outlet pressure of range of 0 to 60 psi, set and locked at
30 psi.
If the tank is within 50 feet of the heater, 5/8” OD, type K copper tubing, or ½” schedule 80 black pipe
should be used for the gas supply line from the vapor regulator on the tank to within 3 feet of the heater, if
the tank is more than 50 feet away, use 7/8” OD type K copper tubing.
CAUTION: The gas storage tank should be at least
25 feet from the heater. Local ordinances may require
further distances.
A high pressure 3 to 5 foot flexible hose for use with
LP gas should be used to connect gas supply line directly
to heater regulator (see diagram A).
The gas supply line should be buried at least 6” below the
ground.
DIAGRAM A