Chapter VIII Maintenance and Preservation
Chapter VIII Maintenane and Preservation
Operation environment requirements
Device operation environment must comply with the operation environment required for the device:
Allowable environment temperature: -20~50
℃
Allowable relative humidity: 0~95% (non-condensing)
Allowable maximum elevation: 3,000m
Note: When exceeding the maximum elevation, the storage inverter will have de-rating output. Please consult customer service
center for specific de-rating coefficient.
Electrical and fixed connection inspection
After being put into operation, conduct regular inspection on device’s electrical and fixed part connection. Such inspection is
advisably conducted every three months. Record for each inspection should be made.
Cabinet grounding connection;
Module grounding connection;
Electrical connection for DC input;
Electrical connection for AC input;
Electrical connection for auxiliary power supply;
Electrical connection for communication cables.
AC/DC switch, SPD and fan.
Access monitored fault information.
Clearing and cleaning
Before the device is put into operation, the dust and sundries in its cooper bars, terminals and mesh openings should be
cleaned.
After the device is put into operation, the dust in machine room should be cleaned regularly. Check whether the ventilating
and air exhaust facilities in machine room are normal. They are advisably cleaned once every three months.
Summary of Contents for PWS1-500KTL-NA
Page 1: ...Sinexcel PWS1 500KTL NA Grid Support Utility Interactive Energy Storage Inverter ...
Page 2: ......
Page 4: ......
Page 7: ...Appendix 2 Quality assurance and after sales service 39 Installation Records 41 ...
Page 8: ......
Page 34: ...26 第六章 操作控制显示面板 6 5 4 AC settings ...
Page 35: ...27 Fig 6 7 AC settings ...
Page 41: ...第六章 操作控制显示面板 33 ...
Page 45: ...Chapter VII Communication Mode 37 Fig 7 5 Structure diagram for background monitoring system ...
Page 49: ...Installation Records ...