31
“Sys ON” and “Sys OFF”.
Control mode
Enter “ctrl mode”. It includes “Local manual”, “Local auto”, “Remote control” and “Lock out” functions.
Fig. 6-11 Control mode
Local manual: Set parameters on the monitoring screen to control machine operation.
Local auto: It is used with “local auto”. Under this mode, monitor and maintain the current parameter setting
(unchangeable), and operate according to the period for “local auto”—power configuration.
Remote control: Under this mode, monitor and maintain the current parameter setting. The parameter setting
can be changed by remote control.
Lock out: Under this mode, monitor and maintain the current parameter setting. The parameter setting
cannot be changed by remote control.
In case of no special requirements, please set it as “local manual” mode.
Tactics
6.8.1
Local strategy
Fig. 6-12 Local strategy