Chapter IV Device Installation 9
AC Rated Current
760A
AC Max Current
836A
Output THDi
≤3%
Power Factor
0~0.8 leading or lagging
AC Stand-alone mode
Voltage
400V
Voltage adjustable range
±10%
Frequency
60Hz(59.5Hz~60.5Hz)
Output THDu
≤2%
(
Linear load
)
System
CEC Efficiency
97%
Wiring Mode
3-Phase 3-Wire
Isolation Mode
Non-isolation
Cooling
Forced air cooling
Noise
70dB
Ambient Temperature.
-20
℃
~50
℃
Protection
IP20 / NEMA1
Max Elevation
3000m
Humidity Range
0~95% (No condensation)
Size (W*H*D)
1100mm*2160mm*800mm
Weight
600kg
COMMUNICATION
Display
Touch Screen
Communication Protocol
Modbus TCP/IP, Modbus RTU
Communication Socket
Ethernet, RS485, CAN
Grid-Support Functions
H/LVRT
Yes
H/LFRT
Yes
Ramp Rate
Yes
Fixed PF
Yes
Volt-Watt
Yes
Volt-Var
Yes
Freq-Watt
Yes
Grid-Support Function
Accuracy
Voltage
1%
Current
1%
(Volt-Watt)Active Power
10%
(Volt-Var)Reactive Power
6%
Frequency
0.02Hz
PF
0.01
Summary of Contents for PWS1-500KTL-NA
Page 1: ...Sinexcel PWS1 500KTL NA Grid Support Utility Interactive Energy Storage Inverter ...
Page 2: ......
Page 4: ......
Page 7: ...Appendix 2 Quality assurance and after sales service 39 Installation Records 41 ...
Page 8: ......
Page 34: ...26 第六章 操作控制显示面板 6 5 4 AC settings ...
Page 35: ...27 Fig 6 7 AC settings ...
Page 41: ...第六章 操作控制显示面板 33 ...
Page 45: ...Chapter VII Communication Mode 37 Fig 7 5 Structure diagram for background monitoring system ...
Page 49: ...Installation Records ...