17
2.4.2 2-Way valve
[Operation Instructions]
At the commissioning parameter setting page, by touching “
Cool 2-Way valve
” or “
Heat 2-Way valve
”, the
control panel will access to the corresponding setting page.
[Notes]
●This setting is unavailable to heating only units.
●Under “
Cool
”, or “
Cool + Hot water
” mode, “
Cool 2-Way valve
” will decide the status of the 2-way valve; while
under “
Heat
” or “
Heat + Hot water
”, “
Heat 2-Way valve
” will decide the status of the 2-way valve.
●It will be memorized upon power failure.
2.4.3 Solar Setting
[Operation Instructions]
1. This setting is unavailable to mini chillers.
2. At the commissioning parameter setting page, by touching “
Solar setting
”, the control panel will access to its
submenu page.
3. At the submenu page, “
Solar setting
” can be set to “
With
” or “
Without
”.
4. At the submenu page, the “
Solar heater
” can be set to “
On
” or “
Off
”.
Solar Setting
[Notes]
●This setting can be done no matter if the unit is turned on or off.
●This setting is allowed only when the water tank is available. When the water tank is unavailable, this setting
will be reserved.
●It will be memorized upon power failure.
2.4.4 Water Tank
[Operation Instructions]
At the commissioning parameter setting page, by touching “
Water tank
”, the control panel will access to the
corresponding setting page, where “Water tank” can be set to “
With
” or “
Without
”.
[Notes]
●This setting will be memorized upon power failure.
●This setting will become valid only when the unit is turned off.
2.4.5 Thermostat
[Operation Instructions]
1. At the commissioning parameter setting page, by touching “Thermostat”, the control panel will access to the
corresponding setting page.
2. At the “
Thermostat”
setting page, it can be set to “
Air
”, “
Without
” or “
Air + hot water
”. When it is set to “
Air
”
or “
Air + hot water”
, the unit will run based on the mode set by the thermostat; when it is set to “
Without
”, the unit