Troubleshooting
Protection of pressure or temp.
Is it K1 or K2 open ?
Is temp. protective switch K1 close
Possible reason
1. The wires is loose to K1
2. Air or other gas in the refrigerant.
3. Heat exchanger is dirty
4. Outdoor fan or fan blade is
defective
5. Outdoor unit is in bad ventilation
6. Refrigerant is leakage
Is pressure protective switch K2 close
Yes
Yes
Yes
Possible reason
1. The wires is loose to K2
2. Air or other gas in the refrigerant.
3. Heat exchanger is dirty
4. Outdoor motor or fan blade is
defective
5. Outdoor unit is in bad ventilation
6. Refrigerant is too much
c. Overload of current
d. Protection of pressure or temp.
Overload of current
Check the current, normally
Is the current in rated range?
The outdoor PCB is defective
Possible reason
1. Outdoor fan is defective
2. The compressor is defective
3. Refrigerant is over charged
4. Air enter the refrigerant system
Yes
No
76
Summary of Contents for ASC-60AN
Page 1: ...SERVICE MANUAL ASF 60AN ASC 60AN ON OFF SERIES ...
Page 2: ......
Page 8: ...Indoor Units Indoor Units Super slim Cassette Type 4 Ceiling Floor Type 17 3 ...
Page 14: ...Dimensions 2 Dimensions Model A H ASC 60AN 287 317 9 ...
Page 15: ...Service Space 3 Service Space 1000mm 1000mm 1000mm 1000m m 10 ...
Page 16: ...Wiring Diagrams 4 Wiring Diagrams ASC 60AN 11 ...
Page 18: ...Sound Levels 6 Sound Levels P Microphone Model Noise level dB A H M L ASC 60AN 55 50 47 13 ...
Page 21: ...Field Wiring 9 Field Wiring ASC 60AN 16 ...
Page 24: ...Dimensions 2 Dimensions Capacity Btu h A B C D E ASF 60AN 1650 675 235 1565 220 19 ...
Page 25: ...Service Space 3 Service Space 20 ...
Page 26: ...Wiring Diagrams 4 Wiring Diagrams ASF 60AN 21 ...
Page 29: ...Field Wiring 9 Field Wiring ASF 60AN 24 ...
Page 34: ...Wiring Diagrams 4 Wiring Diagrams ASF 60AN ASC 60AN 29 ...
Page 76: ...Troubleshooting f Indoor fan speed has been out of control Eb 71 ...
Page 79: ...Troubleshooting c Up down panel is not closed 74 ...
Page 91: ...MODEL ASC 60AN intdoor ...
Page 93: ...Model ASF 60AN indoor ...